Miscellaneous action | | | 4/8/2013 | | DONE |
Tim Frost
|
|
|
Sent to Records for scanning.
|
Miscellaneous action | | | 4/8/2013 | | DONE |
Tim Frost
|
|
|
Sent to Records for scanning.
|
INSP-Final Inspection | 10/24/2012 | 10/25/2012 | 10/24/2012 | A | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Sprinkler Rough-in/Hydro | 8/20/2012 | 8/21/2012 | 8/21/2012 | A | PART |
Forrest France
|
|
|
Overhead hydrostatic test per NFPA completed acceptable. Also verified head location revision at the NW stair landing1st floor.
|
Override - Parcel Holds | 8/20/2012 | 1/1/1900 | 8/20/2012 | | |
|
|
|
this is just for a sprinkler ri
|
INSP-Sprinkler Rough-in | 8/16/2012 | 8/16/2012 | 8/16/2012 | P | PART |
Forrest France
|
|
|
Overhead work approved for cover with the exception of the west stair landing- provide a drop ceiling or relocate the pendent sprinkler to an upright position at the deck. Also need to complete a hydrostatic test per review comments (ref. NFPA 25).
|
Permit Ready to Issue | | | 8/9/2012 | | DONE |
Tisha Gallop
|
|
|
|
Telephone call | | | 8/9/2012 | | DONE |
Tisha Gallop
|
|
|
called Treasure Valley Fire and told them permit is ready and fee.
|
CHANGE STATUS TO (ISS) | | | 8/9/2012 | | DONE |
Tisha Gallop
|
|
|
|
Plan assigned to (Tim) | 8/6/2012 | | 8/8/2012 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 8/8/2012 | | 8/8/2012 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/8/2012 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 8/8/2012 | | 8/8/2012 | | DONE |
Darla L Downs
|
|
|
|
Plan resubmittals received | | | 8/6/2012 | | DONE |
Christina Prado
|
|
|
**PLAN MOD** Received three new sets of plans marked Fp1 of 1; new applications; checklists and calcs. Taken to Tim Frost for review
|
INSP-Final Inspection | 7/19/2012 | 7/20/2012 | 7/20/2012 | A | FAIL |
Troy Cobbley
|
|
|
Ceiling tile has not be installed yet but piping is ok to cover. Actual suite number is 150.
|
Plan assigned to (Tim) | 7/9/2012 | | 7/12/2012 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 7/12/2012 | | 7/12/2012 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 7/12/2012 | | PASS |
Tim Frost
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/12/2012 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 7/12/2012 | | 7/12/2012 | | DONE |
Darla L Downs
|
|
|
|
Permit Ready to Issue | | | 7/12/2012 | | |
|
|
|
|
Telephone call | | | 7/12/2012 | | |
|
|
|
7-12-12 called Brad-Treasure Valle Fire permit ready and fee given ///dld
|
Issue and Print Permit | | | 7/12/2012 | | DONE |
|
|
|
|
Case Summary | | | 7/9/2012 | | DONE |
|
|
|
|
Application received | | | 7/9/2012 | | |
|
|
|
|