Permit Information
Permit NumberFIR12-00365
StatusFinaled
Name PHOENIX FIRE PROTECTION
Site Address 4262 N EAGLE RD
Project NameGRACE BIBLE CHURCH
Customer Number 
ePlanReviewNo
Description
The fire sprinkler scope of work consists of providing protection for the first level of an existing building and a new addition. The existing has existing protection in the attic and basement. The new building will have the protection on the first level and in the attic. Several attic areas are protected with small antifreeze systems. The attic system in the new building utilizes special application sprinklers both single directional and back to back. Large orifice extended coverage sprinklers with 20’x20’ spacing are being used in various locations. The systems are supplied by 4” underground piping through a 4” reduced pressure backflow preventer. There are 4” and 3” mains. The branch lines are predominately 1¼”. The insulation is on the roof deck in the new addition. Therefore, the attic fire protection is a wet pipe system. The existing building fire protection will be connected to the new system. The underground was installed under permit FIR12-00205.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  4/8/2013 DONE
DetailsTim Frost
Sent to Records for scanning.
INSP-Final Inspection1/31/20131/31/20131/31/2013PPASS
DetailsTroy Cobbley
Permit finaled
Plan assigned to (Tim)1/29/2013 1/31/2013 DONE
DetailsTim Frost
Sprinkler Plan Check1/31/2013 1/31/2013 PASS
DetailsTim Frost
Please, see attached comments.
There are NO annotations on the plans.
PLANS/APPL TAKEN TO FRONT DESK  1/31/2013 DONE
DetailsTim Frost
Permit Ready to Issue  1/31/2013 DONE
Inspection Record Card- Fire1/31/2013 1/31/2013 DONE
DetailsTisha Gallop
Telephone call  1/31/2013 DONE
DetailsTisha Gallop
called Phoenix Fire and left mssg for Don plan mod ready and fee due.
CHANGE STATUS TO (ISS)  1/31/2013 DONE
Sprinkler Plan Check1/30/2013 1/30/2013 FAIL
DetailsTim Frost
Please, see attached comments.
There are NO annotations on the plans.
1st review completed  1/30/2013 FAIL
DetailsTim Frost
Telephone call  1/30/2013 DONE
DetailsBarbara Stitt
Called and left message for Don that plans failed and need picked up and re-submitted on 1-30-13 @ 8:55am
Miscellaneous action  1/30/2013 DONE
DetailsTisha Gallop
contractor picked up denied plans
Plan resubmittals received  1/30/2013 DONE
DetailsChristina Prado
received three sets of apps, plans, submittal checklist and related submittal documents; routed to Tim Frost for review
Plan resubmittals received  1/29/2013  
Plan modification
INSP-Sprinkler Rough-in/Hydro1/25/20131/25/20131/25/2013PPASS
DetailsTroy Cobbley
Overhead hydro passed
INSP-Sprinkler Rough-in12/12/201212/12/201212/12/2012PPASS
DetailsTroy Cobbley
See the city approved plans for locations where piping can be covered. I posted a stop work order on the front of the building due to hardlids continuing to be installed prior to a sprinkler rough-in inspection. I had a previous conversation with contractor about this. Stop work order states "Stop all sheet rock that is covering sprinkler piping. Cover inspection is required".
INSP-Supply line flush11/14/201211/14/201211/14/2012PPASS
DetailsTroy Cobbley
The underground supply line flush passed.
INSP-Sprinkler Rough-in11/13/201211/14/201211/14/2012APASS
DetailsTroy Cobbley
The entry lobby sprinkler piping is ok to re-cover. Tim Frost approved as-builts have been marked up by me for location and have been left on the job site with the sprinkler fitter.
INSP-Sprinkler Rough-in11/8/201211/8/201211/8/2012PCANC
DetailsTroy Cobbley
Cancel per Perly Daniel
INSP-Sprinkler Rough-in11/7/201211/7/201211/7/2012PFAIL
DetailsTroy Cobbley
Joe Snyder was requesting a rough-in inspection for the main lobby entry area. I could not give approval due to the piping arrangement not matching the approved plans. The BB heads have been removed and standard coverage upright heads installed. Also the piping has been covered by sheet rock without approval. I spoke to the job site superintendant about a possible stop work order if covering pipe prior to an inspection continued. He agreed that it would not happen again. Plans need to be resubmitted showing the piping changes in all areas and access provided for the following inspection.
INSP-Sprinkler Rough-in10/17/201210/17/201210/17/2012PPASS
DetailsTroy Cobbley
The sprinkler piping in the drive thru canopy can be covered.
INSP-Sprinkler Rough-in9/19/20129/20/20129/20/2012PCANC
DetailsTroy Cobbley
Underground Rough-in. Scott Carter is the contact at ###-####. Phone #: ###-#### >> Inspection requested via web by Kindel de Leon Inspection cancelled from web by: Kindel de Leon
Plan assigned to (Tim)7/12/2012 9/17/2012 DONE
DetailsTim Frost
Sprinkler Plan Check9/17/2012 9/17/2012 PASS
DetailsTim Frost
Please, see attached comments.
There are NO annotations on the plans.
PLANS/APPL TAKEN TO FRONT DESK  9/17/2012 DONE
DetailsTim Frost
Inspection Record Card- Fire9/17/2012 9/17/2012 DONE
DetailsTisha Gallop
Permit Ready to Issue  9/17/2012 DONE
DetailsTisha Gallop
Telephone call  9/17/2012 DONE
DetailsTisha Gallop
Called Phoenix Fire Protection and told recep. permit is ready and fees.
Issue and Print Permit  9/17/2012 DONE
Plan resubmittals received  9/14/2012 DONE
DetailsChristina Prado
Received three sets of plans, submital documents and applications:routed to Tim for further review
Sprinkler Plan Check8/21/2012 8/21/2012 FAIL
DetailsTim Frost
Please, see attached comments.
There are NO annotations on the plans.
Telephone call  8/21/2012 DONE
DetailsChristina Prado
Called Phoenix fire to pick up
Plan resubmittals received  8/20/2012  
Sprinkler Plan Check8/6/2012 8/6/2012 FAIL
DetailsTim Frost
Please, see attached comments.
There are NO annotations on the plans.
Telephone call  8/6/2012  
8-6-12 called Phoenix Fire to pick up///dld
Plan resubmittals received  8/2/2012 DONE
DetailsTisha Gallop
received four copies of application, submittal documents and plans; routed to Fire review.
1st review completed  7/17/2012 FAIL
Sprinkler Plan Check7/17/2012 7/17/2012 FAIL
DetailsTim Frost
Miscellaneous action  7/17/2012 DONE
DetailsTim Frost
Emailed review to contractor
Telephone call  7/17/2012  
7-17-12 called Phoenix Fire permit ready to pick up ///dld
Application received  7/12/2012  
Pending Assignment by SAM7/12/2012 7/12/2012 DONE
DetailsTisha Gallop