Miscellaneous action | | | 10/11/2012 | | DONE |
Tim Frost
|
|
|
Sent to Records for scanning.
|
INSP-Final Inspection | 8/15/2012 | 8/16/2012 | 8/16/2012 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled. Corrections have been made.
|
Telephone call | | | 8/15/2012 | | PASS |
|
|
|
Call from the contractor, said they were using QR Globe k=5.6 in lieu of QR Reliable k=5.6 in the prep area. I told him they were ok
|
INSP-Sprinkler Rough-in | 8/9/2012 | 8/10/2012 | 8/10/2012 | A | FAIL |
Troy Cobbley
|
|
|
Pendant heads and upright heads are located too close to one another in two locations as marked on the plans. The dry pendants need to be foamed. Remove tape/paper from the upright heads. The control valve to the anti-freeze system has been shut for an unknown reason. The sprinkler heads SIN number installed does not match what was submitted. Information needs to be submitted for the change.
|
Permit Ready to Issue | | | 7/24/2012 | | DONE |
|
|
|
|
Issue and Print Permit | | | 7/24/2012 | | DONE |
|
|
|
|
Plan assigned to (Tim) | 7/16/2012 | | 7/18/2012 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 7/18/2012 | | 7/18/2012 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 7/18/2012 | | PASS |
Tim Frost
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/18/2012 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 7/18/2012 | | 7/18/2012 | | DONE |
Darla L Downs
|
|
|
|
Case Summary | | | 7/16/2012 | | DONE |
Christina Prado
|
|
|
|
Application received | | | 7/16/2012 | | |
|
|
|
|