Case Summary | | | 2/18/2016 | | DONE |
|
|
|
|
Miscellaneous action | | | 9/26/2012 | | DONE |
|
|
|
Plans taken to records for scanning.
|
INSP-Final Inspection | 9/4/2012 | 9/7/2012 | 9/7/2012 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Alarm Testing | 8/27/2012 | 8/27/2012 | 8/27/2012 | P | FAIL |
Troy Cobbley
|
|
|
One of the two strobes needed the candella increased to meet code while I waited. When the manual pull station was activated the horn strobes did not activate. Inspection failed. Also need updated as-builts showing the relocated strobe and the one with the increased candella.
|
INSP-Final Inspection | 8/21/2012 | 8/24/2012 | 8/24/2012 | P | CANC |
Troy Cobbley
|
|
|
Chris and I agreed to reschedule this test for monday afternoon since I am overbooked.
|
Issue and Print Permit | | | 7/20/2012 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 7/16/2012 | | 7/18/2012 | | DONE |
Stephanie L. Cobbley
|
|
|
|
1st review completed | | | 7/18/2012 | | PASS |
|
|
|
|
Alarm Plan Check | 7/18/2012 | | 7/18/2012 | | PASS |
Stephanie L. Cobbley
|
|
|
Quick permit plans approved with redlines - no written review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 7/18/2012 | | DONE |
|
|
|
Approved redlined quick permit plans taken to permit technician for processing.
|
Inspection Record Card- Fire | 7/18/2012 | | 7/18/2012 | | DONE |
Darla L Downs
|
|
|
|
Permit Ready to Issue | | | 7/18/2012 | | |
|
|
|
|
Telephone call | | | 7/18/2012 | | |
|
|
|
7-18-12 called ChriSonitrol Pacific permit ready and fee given ///dld
|
Case Summary | | | 7/16/2012 | | DONE |
|
|
|
|
Application received | | | 7/16/2012 | | |
Barbara Stitt
|
|
|
|