Miscellaneous action | | | 9/26/2012 | | DONE |
|
|
|
Plans taken to records for scanning.
|
INSP-Final Inspection | 8/17/2012 | 8/20/2012 | 8/20/2012 | A | PASS |
Forrest France
|
|
|
Noted corrections verified for completion. Fire alarm permit finaled.
|
INSP-Final Inspection | 8/15/2012 | 8/16/2012 | 8/16/2012 | P | FAIL |
Troy Cobbley
|
|
|
All items tested ok except the sound did not sync as required per NFPA 72. Brian stated that he was going to change out the devices and reschedule.
|
Issue and Print Permit | | | 8/6/2012 | | |
|
|
|
|
Plan assigned to (Stephanie) | 7/24/2012 | | 8/3/2012 | | DONE |
Stephanie L. Cobbley
|
|
|
|
1st review completed | | | 8/3/2012 | | PASS |
|
|
|
|
Alarm Plan Check | 8/3/2012 | | 8/3/2012 | | PASS |
Stephanie L. Cobbley
|
|
|
Plans approved with redlines and review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 8/3/2012 | | DONE |
|
|
|
Approved redlined plans taken to permit technician for processing.
|
Override - Parcel Holds | | | 8/3/2012 | | |
|
|
|
|
Permit Ready to Issue | | | 8/3/2012 | | |
|
|
|
|
Override - Parcel Holds | | | 8/3/2012 | | |
|
|
|
|
Override - Parcel Holds | | | 8/3/2012 | | |
|
|
|
|
Inspection Record Card- Fire | 8/3/2012 | | 8/3/2012 | | DONE |
Darla L Downs
|
|
|
|
Telephone call | | | 8/3/2012 | | |
|
|
|
8-3-12 called Brian-Local Fire & Security permit ready and fee given ///dld
|
Case Summary | | | 7/24/2012 | | DONE |
Barbara Stitt
|
|
|
|
Application received | | | 7/24/2012 | | |
|
|
|
|