Miscellaneous action | | | 9/26/2012 | | DONE |
|
|
|
Plans taken to records for scanning.
|
INSP-Final Inspection | 8/28/2012 | 8/28/2012 | 8/28/2012 | P | PASS |
Forrest France
|
|
|
Fire alarm permit finaled.
|
INSP-Alarm Testing | 8/24/2012 | 8/28/2012 | 8/28/2012 | P | PASS |
Forrest France
|
|
|
Scope of fire alarm work passed functional testing.
|
Issue and Print Permit | | | 8/16/2012 | | DONE |
|
|
|
|
Plan resubmittals received | | | 8/14/2012 | | DONE |
Tisha Gallop
|
|
|
received two copies of application and submittal docs; routed to Fire
|
Alarm Plan Check | 8/14/2012 | | 8/14/2012 | | PASS |
Stephanie L. Cobbley
|
|
|
Quick permit 2nd resubmittal approved with redlines - no written review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 8/14/2012 | | DONE |
|
|
|
Approved quick permit (2nd resubmittal) redlined plans taken to permit technician for processing.
|
Miscellaneous action | | | 8/14/2012 | | DONE |
|
|
|
emailed Simplexgrinnell to let them know the plans have been approved and they have been handed over to the permit technicians for processing.
|
Inspection Record Card- Fire | 8/14/2012 | | 8/14/2012 | | DONE |
Darla L Downs
|
|
|
|
Permit Ready to Issue | | | 8/14/2012 | | |
|
|
|
|
Telephone call | | | 8/14/2012 | | |
|
|
|
8-14-12 called Tara- Simplex Grinnell permit ready and fee given ///dld
|
Plan assigned to (Stephanie) | 8/2/2012 | | 8/14/2012 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Plan resubmittals received | | | 8/13/2012 | | DONE |
Christina Prado
|
|
|
Received 1 new application, checklist and calcs; taken to Stephanie for review
|
Telephone call | | | 8/13/2012 | | DONE |
|
|
|
Spoke to Charlie at Simplexgrinnell to go over the resubmitted quick permit plans. I explained that by relocating an existing device from the crew room area to the Quiet Room, portions of the Crew Room were left without adequate visual coverage. I let him know I would need to reject the plans because regardless of how they decide to approach providing additional coverage new battery calculations and voltage drops would be required. He said he understood. I let him know a copy of the redlined plans would be available at the permit desk for him to pick up.
|
Alarm Plan Check | 8/13/2012 | | 8/13/2012 | | FAIL |
Stephanie L. Cobbley
|
|
|
Quick permit resumittal denied
|
Miscellaneous action | | | 8/13/2012 | | DONE |
|
|
|
Denied redlined plans taken to permit desk for contractor to pick up.
|
Telephone call | | | 8/13/2012 | | DONE |
|
|
|
Spoke to Jeff Creek to let him know the plans have been denied and that there are redlined plans available at the permit desk to pick up. I let him know that I had contacted Simplexgrinnell to go over the deficiencies.
|
Telephone call | | | 8/10/2012 | | DONE |
|
|
|
Dante with Simplexgrinnell called. He said they ran the calculations and the circuit they show the new device added to is maxed out and will not accomodate the device as submitted. I explained I would need to fail the permit. He said he should have the new documentation to me next week after their technician is back from vacation and can go to the site and survey the actual current draws/speaker circuit watts etc...
|
Alarm Plan Check | 8/10/2012 | | 8/10/2012 | | FAIL |
Stephanie L. Cobbley
|
|
|
Plans denied due to phone conversation with Simplexgrinnell stating the submitted circuiting is not accurate.
|
1st review completed | | | 8/7/2012 | | FAIL |
|
|
|
|
Application received | | | 8/2/2012 | | DONE |
Barbara Stitt
|
|
|
|