Miscellaneous action | | | 11/30/2012 | | DONE |
|
|
|
Plans taken to records for scanning.
|
INSP-Final Inspection | 11/13/2012 | 11/14/2012 | 11/14/2012 | P | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Alarm Testing | 11/7/2012 | 11/8/2012 | 11/8/2012 | A | PART |
Troy Cobbley
|
|
|
A temporary occupancy was given until the fire alarm permit/correction issues have been addressed.
|
Plan assigned to (Stephanie) | 11/6/2012 | | 11/7/2012 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Alarm Plan Check | 11/7/2012 | | 11/7/2012 | | PASS |
Stephanie L. Cobbley
|
|
|
Plan modification approved with review comments and redlines
|
PLANS TAKEN FRONT DESK ALARM | | | 11/7/2012 | | DONE |
|
|
|
Approved plan review documents taken to permit technician for processing.
|
Inspection Record Card- Fire | 11/7/2012 | | 11/7/2012 | | DONE |
Tisha Gallop
|
|
|
|
Permit Ready to Issue | | | 11/7/2012 | | |
|
|
|
|
Telephone call | | | 11/7/2012 | | DONE |
Tisha Gallop
|
|
|
called Jason and left mssg plan mod is ready and fee.
|
(F) Reprint permit | | | 11/7/2012 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 11/7/2012 | | DONE |
|
|
|
|
INSP-Final Inspection | 11/5/2012 | 11/6/2012 | 11/6/2012 | P | CANC |
Troy Cobbley
|
|
|
No testing was performed due to the plans needing resubmitted. I also noted door magnets that have been installed within the past week that are not connected to the fire alarm system as required per IFC 1008.1.4.4.
|
Plan resubmittals received | | | 11/6/2012 | | DONE |
Tisha Gallop
|
|
|
Plan Modification: received application and two copies of submittal folder and plans; routed to Fire
|
INSP-Final Inspection | 10/29/2012 | 10/29/2012 | 10/29/2012 | P | FAIL |
Troy Cobbley
|
|
|
All items tested except for the smoke detector over the main facp, duct smoke detectors and all notification items. Plans need to be resubmitted showing the correct NAC panels installed, audio/visuals have been added, candellas have been changed, audio/visual devices are overspaced and some are mounted too high. The manual pull station is mounted too high as well. Signals were verified through the Peak Alarm guard at the gate.
|
Permit Ready to Issue | | | 8/23/2012 | | |
|
|
|
|
Issue and Print Permit | | | 8/23/2012 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 8/8/2012 | | 8/21/2012 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Plan assigned to (Stephanie) | 8/8/2012 | | 8/21/2012 | | DONE |
Stephanie L. Cobbley
|
|
|
|
1st review completed | | | 8/21/2012 | | PASS |
|
|
|
|
Alarm Plan Check | 8/21/2012 | | 8/21/2012 | | PASS |
Stephanie L. Cobbley
|
|
|
Plans approved with redlines and review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 8/21/2012 | | DONE |
|
|
|
Approved redlined plans taken to permit technician for processing.
|
Inspection Record Card- Fire | 8/21/2012 | | 8/21/2012 | | DONE |
Darla L Downs
|
|
|
|
Application received | | | 8/8/2012 | | |
|
|
|
|