Permit Information
Permit NumberFIR12-00451
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 401 S BROADWAY AVE
Project NameWhole Foods
Customer Number 
ePlanReviewNo
Description
The fire sprinkler scope of work consists of tenant finish out of a grocery/restaurant store. Sprinklers are being armed over and several new branch lines are being added. Pendent sprinklers are being added in the new ceiling areas from the above existing branch lines. The building is approximately 28’ high. However, the fire protection system is designed for ordinary hazard group II. This limits the height of storage to 12’ per NFPA.

The original shell sprinklers were installed under permit FIR12-00094
The fire protection underground supply was installed under permit FIR12-00020
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/31/201211/1/201211/1/2012APASS
DetailsForrest France
Final inspection passed. Fire sprinkler permit final approved.
INSP-Final Inspection10/19/201210/22/201210/30/2012APART
DetailsForrest France
Completed final system walkthrough. Verified sprinkler monitoring, forward flow test finished. Items noted include; missing escutcheons, travel caps, head cages at uprights below 7', need to install intermediate temp heads at the skylights (8 locations), caps at end mains to remain accessible. Note- some items finished while on site.
INSP-Sprinkler Rough-in10/15/201210/16/201210/30/2012PPART
DetailsForrest France
See dated plan annotations
INSP-Sprinkler Rough-in/Hydro10/19/201210/19/201210/22/2012APEND
DetailsForrest France
INSP-Sprinkler Rough-in10/15/201210/15/201210/16/2012PPART
DetailsForrest France
Okay to cover pendent heads at the seafood area grid ceilings and the second floor corridor sheetrock ceiling.
INSP-Sprinkler Rough-in10/9/201210/9/201210/9/2012PPART
DetailsForrest France
Pendent heads at the grid ceilings main level including the kitchen and service counter areas okay for cover.
INSP-Sprinkler Rough-in9/26/20129/26/20129/26/2012PPART
DetailsForrest France
Grid ceiling areas on the second floor and sheetrock soffit at the sw main level okay for cover.
INSP-Sprinkler Rough-in9/17/20129/17/20129/17/2012APART
DetailsForrest France
Branchline piping to SW heads at the storefront canopy okayed for cover.
INSP-Sprinkler Rough-in9/13/20129/14/20129/14/2012APART
DetailsForrest France
Inspection for cover at the plan modification area okay for cover. Completed shell rough-in inspection, noted areas to maintain coverage between uprights and full height walls.
INSP-Sprinkler Rough-in/Hydro9/6/20129/7/20129/7/2012APASS
DetailsTroy Cobbley
The sprinkler piping clouded in red on the modified plans is ok to cover given todays date. I noted that the 4" main, as marked on the plans has additional elbows which may require another plan modification to verify hydraulic calculations.
Permit Ready to Issue  9/6/2012 DONE
CHANGE STATUS TO (ISS)  9/6/2012 DONE
(F) Reprint permit  9/6/2012 DONE
INSP-Conference8/28/20128/29/20129/5/2012ADONE
DetailsForrest France
On site conference with contractor regarding sprinkler coverage at exterior canopies to meet the guidelines and requirements of NFPA 13 2010 sections 8.15.7.1, 8.15.7.2, 8.15.7.3, and 8.15.7.5. Any alternate proposals or methods to these conditions must be approved by the fire code official per IFC 2009 104.9.
Plan assigned to (Tim)9/4/2012 9/5/2012 DONE
DetailsTim Frost
Sprinkler Plan Check9/5/2012 9/5/2012 PASS
DetailsTim Frost
Please, see attached comments.
There are NO annotations on the plans.
PLANS/APPL TAKEN TO FRONT DESK  9/5/2012 DONE
DetailsTim Frost
Inspection Record Card- Fire9/5/2012 9/5/2012 DONE
DetailsAlexandra L. DeYoung
Plan resubmittals received  9/4/2012 DONE
DetailsChristina Prado
**PLAN MOD*** received 3 revised sets of drawings, applications and calcs. Taken to Tim Frost for review
INSP-Sprinkler Rough-in8/28/20128/29/20128/29/2012APART
DetailsForrest France
Overhead work at the second floor elevator machine room and four office rooms okayed for ceiling cover, also approved rough-in at the new 2" branch line and drops to the produce cooler and ceilings in the specialty area.
INSP-Conference8/27/20128/29/20128/28/2012ACANC
DetailsTroy Cobbley
Would like to review permit comments in regards to field verification of exterior canopy protection. Please call cell phone with time frame. Thanks, Jeff Packham. Phone #: ###-#### >> Inspection requested via web by Jeff Packham Inspection cancelled from web by: Jeff Packham
Issue and Print Permit  8/20/2012 DONE
Plan assigned to (Tim)8/15/2012 8/16/2012 DONE
DetailsTim Frost
Sprinkler Plan Check8/16/2012 8/16/2012 PASS
DetailsTim Frost
Please, see attached comments.
There are NO annotations on the plans.
1st review completed  8/16/2012 PASS
DetailsTim Frost
PLANS/APPL TAKEN TO FRONT DESK  8/16/2012 DONE
DetailsTim Frost
Telephone call  8/16/2012 DONE
DetailsChristina Prado
Called Brad to advise permit is ready
Inspection Record Card- Fire8/16/2012 8/16/2012 DONE
DetailsChristina Prado
Permit Ready to Issue  8/16/2012 DONE
DetailsChristina Prado
Application received  8/15/2012 DONE
DetailsBarbara Stitt
Case Summary  8/15/2012 DONE
DetailsBarbara Stitt