Miscellaneous action | | | 2/14/2013 | | DONE |
|
|
|
Plans taken to records for scanning
|
INSP-Final Inspection | 1/11/2013 | 1/11/2013 | 1/11/2013 | A | PASS |
Forrest France
|
|
|
Fire alarm work passed final inspection.
|
INSP-Final Inspection | 1/10/2013 | 1/10/2013 | 1/11/2013 | P | PART |
Forrest France
|
|
|
Plan modification verified.
|
(F) Reprint permit | | | 1/10/2013 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 1/10/2013 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 1/3/2013 | | 1/9/2013 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Alarm Plan Check | 1/9/2013 | | 1/9/2013 | | PASS |
Stephanie L. Cobbley
|
|
|
Plan modification approved with redlines and review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 1/9/2013 | | DONE |
|
|
|
Approved plan modifications taken to permit technician for processing.
|
Telephone call | | | 1/9/2013 | | DONE |
Christina Prado
|
|
|
|
Inspection Record Card- Fire | 1/9/2013 | | 1/9/2013 | | DONE |
Christina Prado
|
|
|
|
Permit Ready to Issue | | | 1/9/2013 | | DONE |
Christina Prado
|
|
|
|
INSP-Final Inspection | 1/3/2013 | 1/4/2013 | 1/4/2013 | P | PART |
Troy Cobbley
|
|
|
A temporary occupancy for the new construction area was given with scott arellano's permission until the project related fire alarm permit has been re-issued. It is at the fire inspectors discression to require EOL verification when the plans are re-issued.
|
Plan resubmittals received | | | 1/3/2013 | | |
|
|
|
plan modification
|
INSP-Final Inspection | 11/26/2012 | 11/27/2012 | 11/27/2012 | P | NR |
Forrest France
|
|
|
Final pending completion of remodel work.
|
Issue and Print Permit | | | 9/13/2012 | | DONE |
Barbara Stitt
|
|
|
|
Application received | | | 9/10/2012 | | DONE |
Barbara Stitt
|
|
|
Plans were actually received 8-31-12//BAS
|
Plan assigned to (Stephanie) | 9/10/2012 | | 9/10/2012 | | DONE |
Stephanie L. Cobbley
|
|
|
|
1st review completed | | | 9/10/2012 | | PASS |
|
|
|
|
Alarm Plan Check | 9/10/2012 | | 9/10/2012 | | PASS |
Stephanie L. Cobbley
|
|
|
Plans approved with redlines and review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 9/10/2012 | | DONE |
|
|
|
Approved redlined plans taken to permit technician for processing.
|
Telephone call | | | 9/10/2012 | | DONE |
Christina Prado
|
|
|
Called john to advise permit is ready
|
Inspection Record Card- Fire | 9/10/2012 | | 9/10/2012 | | DONE |
Christina Prado
|
|
|
|
Permit Ready to Issue | | | 9/10/2012 | | DONE |
Christina Prado
|
|
|
|