Miscellaneous action | | | 12/26/2012 | | DONE |
|
|
|
plans taken to records for scanning.
|
INSP-Final Inspection | 11/30/2012 | 12/3/2012 | 12/3/2012 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled. Per Scott with Quality Electric the audible wire to the speakers had been damaged and was now repaired.
|
INSP-Final Inspection | 11/26/2012 | 11/27/2012 | 11/27/2012 | A | FAIL |
Troy Cobbley
|
|
|
When the new smoke detector was tested the strobes activated but the horns/voice evac did not. I verified candella and spacing for the new devices. To pass inspection the audible portion of the fire alarm system needs to function and the heat detector needs to be tested. I also noted three existing smoke detectors located too close to supply/return air grills. This item has been turned over to the fire dept. for follow-up.
|
Issue and Print Permit | | | 10/5/2012 | | DONE |
Barbara Stitt
|
|
|
|
Plan assigned to (Stephanie) | 9/11/2012 | | 9/18/2012 | | DONE |
Stephanie L. Cobbley
|
|
|
|
1st review completed | | | 9/18/2012 | | PASS |
|
|
|
|
Alarm Plan Check | 9/18/2012 | | 9/18/2012 | | PASS |
Stephanie L. Cobbley
|
|
|
Plans approved with redlines and review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 9/18/2012 | | DONE |
|
|
|
Approved redlined plans taken to permit technician for processing.
|
Telephone call | | | 9/18/2012 | | DONE |
Christina Prado
|
|
|
called Mark to advise permit is ready and fees are due
|
Inspection Record Card- Fire | 9/18/2012 | | 9/18/2012 | | DONE |
Christina Prado
|
|
|
|
Permit Ready to Issue | | | 9/18/2012 | | DONE |
Christina Prado
|
|
|
|
Application received | | | 9/11/2012 | | |
|
|
|
|
Case Summary | | | 9/11/2012 | | DONE |
|
|
|
|