Permit Information
Permit NumberFIR12-00511
StatusFinaled
Name NORTHWEST SECURITY INC
Site Address 7990 W OVERLAND RD
Project NameLowe's
Customer Number 
ePlanReviewNo
Description
This quick permit is to relocate and existing horn/strobe from a room previously used as a manager's office to an ajoining new manager's office, and to relocate an existing pull station and remote annunciator from outside the new manager's office to the entry/battery area. Approval is subject to field measurement of the EOL voltage drop. the minimum acceptable voltage is 21.6V with the AC power off. Any measurement below this voltage will be considered insufficient to run the NACs at the end of useful battery life of 20.4V (per UL 864, Standard for Control Units for Fire Signaling Systems). See NFPA 72 2010 Handbook 18.3.2.3 for further assistance with calculations. The installing contractor shall have available at final inspection a voltage meter and measure end of line voltages; witnessed by the field inspector. There are no written review comments. There is no associated building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  9/27/2012 DONE
plans taken to records for scanning
INSP-Final Inspection9/25/20129/26/20129/26/2012APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection9/21/20129/21/20129/21/2012PFAIL
DetailsTroy Cobbley
Waited at the job site with Randy but manager did not come up front to help with the reset codes. So no inspection was performed.
Issue and Print Permit  9/17/2012 DONE
DetailsBarbara Stitt
Application received  9/12/2012  
Plan assigned to (Stephanie)9/12/2012 9/12/2012 DONE
DetailsStephanie L. Cobbley
1st review completed  9/12/2012 PASS
Alarm Plan Check9/12/2012 9/12/2012 PASS
DetailsStephanie L. Cobbley
Quick permit approved with redlines - no written review comments.
PLANS TAKEN FRONT DESK ALARM  9/12/2012 DONE
Approved quick permit documents taken to permit technician for processing.
Inspection Record Card- Fire9/12/2012 9/12/2012 DONE
DetailsDarla L Downs
Permit Ready to Issue  9/12/2012  
Telephone call  9/12/2012  
9-12-12 called Northwest security permit ready and fee given ///dld