Information based on query as of Thursday, July 25, 2024.
Permit Information
Permit NumberFIR12-00519
StatusFinaled
Name NORTHWEST SALES COMPANY
Site Address 101 S CAPITOL BLVD Unit: 610
Project NameUS Bank - 6th Floor
Customer Number 
ePlanReviewNo
Description
This quick permit is to relocate an existing strobe and increase its candela rating from 15cd to 30cd due to two office areas being converted into one new conference room. Approval is subject to field measurement of the EOL voltage drop. The voltage drop calculations are based on a 10% drop, therefore the minimum acceptable voltage is 21.6V with the AC power off. Any measurement below this voltage will be considered insufficient to run the NACs at the end of useful battery life of 20.4V (per UL 864, Standard for Control Units for Fire Signaling Systems). See NFPA 72 2010 Handbook 18.3.2.3 for further assistance with calculations. The installing contractor shall have available at final inspection a voltage meter and measure end of line voltages; witnessed by the field inspector. There are no written review comments. Associated building permit: BLD12-01653
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  9/27/2012 DONE
plans taken to records for scanning
INSP-Final Inspection9/24/20129/25/20129/25/2012APASS
DetailsTroy Cobbley
permit finaled.
Issue and Print Permit  9/19/2012 DONE
Plan assigned to (Stephanie)9/13/2012 9/17/2012 DONE
DetailsStephanie L. Cobbley
1st review completed  9/17/2012 PASS
Alarm Plan Check9/17/2012 9/17/2012 PASS
DetailsStephanie L. Cobbley
Quick permit approved - no written review comments.
PLANS TAKEN FRONT DESK ALARM  9/17/2012 DONE
Approved quick permit plans taken to permit technician for processing.
Inspection Record Card- Fire9/17/2012 9/17/2012 DONE
DetailsChristina Prado
Permit Ready to Issue  9/17/2012 DONE
DetailsChristina Prado
Telephone call  9/17/2012  
Called David to advise permit is ready
Application received  9/13/2012