Miscellaneous action | | | 12/3/2012 | | DONE |
|
|
|
Plans taken to records for scanning.
|
INSP-Final Inspection | 11/14/2012 | 11/14/2012 | 11/14/2012 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled. The duct smoke detector power is now supplied from a separater 110 volt circuit and not from the fire alarm control panel.
|
INSP-Final Inspection | 11/8/2012 | 11/8/2012 | 11/8/2012 | P | FAIL |
Troy Cobbley
|
|
|
The new duct smoke detectors are powered from the fire alarm control panel which is not noted on the plans. Per the plan reviewer revised calculations are required showing the addtional power loss prior to a final sign off. HVAC units were tested for shutdown which passed.
|
Issue and Print Permit | | | 11/7/2012 | | DONE |
Barbara Stitt
|
|
|
|
Telephone call | | | 11/2/2012 | | DONE |
Christina Prado
|
|
|
|
Inspection Record Card- Fire | 11/2/2012 | | 11/2/2012 | | DONE |
Christina Prado
|
|
|
|
Permit Ready to Issue | | | 11/2/2012 | | DONE |
Christina Prado
|
|
|
|
Plan assigned to (Stephanie) | 10/22/2012 | | 11/1/2012 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Alarm Plan Check | 11/1/2012 | | 11/1/2012 | | PASS |
Stephanie L. Cobbley
|
|
|
Plan modification approved with redlines and review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 11/1/2012 | | DONE |
|
|
|
Approved plan modification documents taken to permit technician for processing.
|
INSP-Final Inspection | 10/19/2012 | 10/22/2012 | 10/22/2012 | P | FAIL |
Troy Cobbley
|
|
|
The electric alarm bell has not been installed yet. Plan modifications are required for the four duct smoke detectors that were not included on the original submittal. The sample tubes currently installed are too short. Need breaker lock installed. The manual pull station installed is not the same as the submittal though it is addressable and does function.
|
Plan resubmittals received | | | 10/22/2012 | | DONE |
Tisha Gallop
|
|
|
Plan Modification: Received two copies of application, submittal folder and plans; routed to Stephanie Cobbley.
|
Override - Parcel Holds | | | 9/26/2012 | | |
|
|
|
|
Issue and Print Permit | | | 9/26/2012 | | DONE |
Tisha Gallop
|
|
|
|
Plan assigned to (Stephanie) | 9/21/2012 | | 9/25/2012 | | DONE |
Stephanie L. Cobbley
|
|
|
|
1st review completed | | | 9/25/2012 | | PASS |
|
|
|
|
Alarm Plan Check | 9/25/2012 | | 9/25/2012 | | PASS |
Stephanie L. Cobbley
|
|
|
Plans approved with redlines and review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 9/25/2012 | | DONE |
|
|
|
Approved redlined plans taken to permit technician for processing.
|
Override - Parcel Holds | | | 9/25/2012 | | |
|
|
|
|
Inspection Record Card- Fire | 9/25/2012 | | 9/25/2012 | | DONE |
Tisha Gallop
|
|
|
|
Override - Parcel Holds | | | 9/25/2012 | | |
|
|
|
|
Permit Ready to Issue | | | 9/25/2012 | | DONE |
Tisha Gallop
|
|
|
|
Telephone call | | | 9/25/2012 | | DONE |
Tisha Gallop
|
|
|
called Peak Alarm and told Mike permit is ready and fee.
|
Application received | | | 9/21/2012 | | |
|
|
|
|