Permit Information
Permit NumberFIR12-00549
StatusFinaled
Name DOHERTY ELECTRIC
Site Address 150 N CAPITOL BLVD
Project NameBoise City Hall 3rd Floor Remo
Customer Number 
ePlanReviewNo
Description
5/2/13 Plan Modification (no initiating devices affected): This plan modification is to incorporate field changes, implement previous redlines and review comments, and to include control modules for door holder release and lighting control.
10/8/12: This fire alarm permit is to replace two existing remote power supplies with new Potter series panels; replace and add notification devices, provide full area smoke detection for f/s damper shutdown, provide heat detectors in areas that would be problematic to smoke detectors, provide two new pull stations, and provide duct detectors and control modules for HVAC monitoring/shutdown. A synchronization module is being provided to ensure audible/visual synchronization throughout the third floor.
Associated building permit: BLD11-02317
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Case Summary  1/31/2014 DONE
Case Summary  1/23/2014 DONE
Miscellaneous action  9/24/2013 DONE
Documents scanned into Onbase and Tidemark
Plan resubmittals received  5/31/2013 DONE
DetailsTisha Gallop
One copy (2 plan sheets) of as-builts provided by contractor, taken to Troy Cobbley
Meeting  5/28/2013 DONE
Had a meeting with Bruce of CM Company regarding as-built requirements for the 3rd floor. His specific question was with regard to the existing magnetic door holders that release upon general alarm. Previously, these devices were not shown on the plans. I explained that typically, door release functions after the fact would require a plan modification. However, under the circumstances that the door holders were part of the original system, just not shown on the plans, I verified that the door holders could be indicated on the as-built drawings. I explained that they would need to be shown on the floorplans, on the one-line, and in the I/O matrix. We discussed that a portion of the building remodel was to ensure we have an accurate record of the system. Therefore, this must be included in the as-built drawings and documentation.
Case Summary  5/20/2013 DONE
INSP-Final Inspection5/7/20135/9/20135/9/2013APASS
DetailsTroy Cobbley
Permit finaled. I need as-builts showing the added heat detector, new a/v and the interconnection to the existing door mags....ect.
Permit Ready to Issue  5/3/2013  
Inspection Record Card- Fire5/3/2013 5/3/2013 DONE
DetailsDarla L Downs
Telephone call  5/3/2013  
5-3-13 called Mike -Doherty Electric permit ready and fee given ///dld
CHANGE STATUS TO (ISS)  5/3/2013 DONE
Plan assigned to (Stephanie)4/9/2013 5/2/2013 DONE
DetailsStephanie L. Cobbley
Plan Modification
Alarm Plan Check5/2/2013 5/2/2013 PASS
DetailsStephanie L. Cobbley
Plan modification resubmittal approved with redlines and review comments.
PLANS TAKEN FRONT DESK ALARM  5/2/2013 DONE
Approved plans taken to permit technician for processing.
Plan resubmittals received  5/1/2013  
5-1-13 received 1 application,2 files & 4 sheets/plans sent to SLC
Alarm Plan Check4/23/2013 4/23/2013 FAIL
DetailsStephanie L. Cobbley
Plan modifications denied - many of the previous redlines have not been implemented, and floorplan layout changes discussed in the email have not been shown.
Miscellaneous action  4/23/2013 DONE
Faxed review comments to the applicant.
Miscellaneous action  4/22/2013 DONE
Applicant brought in revised plans, however they do not reflect any of the redlines or changes discussed.
Miscellaneous action  4/16/2013 DONE
Emailed the applicant because several redlines from the previous review were not implemented into the plan modification set. He emailed back stating that some of the redlines were implemented in the field but were not transferred to the drawings. He also forwarded an email from the contractor stating that some walls were incorrect and device locations and counts are incorrect. I explained to the applicant that I could not approved the plan modifications unless they match the installation. I let him know that I would not fail the plans yet but I would need revised drawings and calcs by Friday, 4/19/13.
Plan resubmittals received  4/9/2013 DONE
DetailsTisha Gallop
Plan Modification: Received two copies of application, submittal folder and plans; routed to Fire Review.
INSP-Conference4/4/20134/5/20134/5/2013ACANC
DetailsForrest France
Bruce CM co. phone #: ###-#### Inspection cancelled from web by: Shawna Gates
Telephone call  3/19/2013 DONE
Rob with Protex called. He stated that the following changes have been made:
1.Eliminate the (3) duct detectors in the council chambers
2.Add a relay module for lighting control in the council chambers
And wanted to know if a resubmittal required?
I let him know if those are the only modifications, then as-built drawings should cover it. I asked him to please ensure the original comments/redlines have been implemented and calcs/voltage drops revised, as well as updating the operations matrix. Subject to inspector approval.
FIR-Aging Inspection2/28/20132/28/20132/28/2013 DONE
DetailsForrest France
Work in progress
INSP-Alarm Testing11/13/201211/15/201211/14/2012ACANC
DetailsTroy Cobbley
We need to schedule a fire alarm test for the 1st main lobby and misc. offices at Boise city hall, we need to start at 7am. please call mike to confirm ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates Inspection cancelled from web by: Shawna Gates
Override - Parcel Holds  10/9/2012  
Issue and Print Permit  10/9/2012 DONE
DetailsBarbara Stitt
Plan assigned to (Stephanie)9/25/2012 10/8/2012 DONE
DetailsStephanie L. Cobbley
1st review completed  10/8/2012 PASS
Alarm Plan Check10/8/2012 10/8/2012 PASS
DetailsStephanie L. Cobbley
Plans approved with redlines and review comments - asbuilt drawings and documents required at time of final inspection
PLANS TAKEN FRONT DESK ALARM  10/8/2012 DONE
Approved redlined plans taken to permit technician for processing.
Override - Parcel Holds  10/8/2012  
Permit Ready to Issue  10/8/2012 DONE
DetailsTisha Gallop
Override - Parcel Holds  10/8/2012  
Inspection Record Card- Fire10/8/2012 10/8/2012 DONE
DetailsTisha Gallop
Override - Parcel Holds  10/8/2012  
Permit Ready to Issue  10/8/2012 DONE
DetailsTisha Gallop
Telephone call  10/8/2012 DONE
DetailsTisha Gallop
called Doherty Elec and told her permit is ready and fee.
Miscellaneous action  10/5/2012 DONE
Received room names/uses
Miscellaneous action  10/4/2012 DONE
Recieved an email with generic areas defined.
Meeting  10/4/2012 DONE
Had a brief meeting with R. Bousfeild and explained the detail I need for the room use. He stated that now that he knows what I need, he will get the information for me by tomorrow.
Telephone call  10/2/2012 DONE
Left a message for Chris Curtis requesting the room names and uses for the third floor.
Telephone call  9/28/2012 DONE
Chris with CH2MHill called. He stated the full area smoke detection is for fire/smoke damper shut down in case they get to the end of the project and found fire/smoke dampers. I expresed concern over providing detection when it is not certain that the f/s dampers even exist. I also expressed concern because the panel signal circuits are getting very full. He said they would just add another panel if needed. He has opted to stay with the submitted design of full area smoke detection for f/s damper shutdown. I requested an email or fax of the room names so I can verify room use for detection and notification purposes. He said he would get me the information right away.
Telephone call  9/26/2012 DONE
Left Bret w/CH2MHill a message to ask about the intended use of the non-required smoke detectors.
Meeting  9/26/2012 DONE
Met with Rob Bousfield to go over possible issues with non-required proposed smoke detecton maxing out the existing fire alarm panels
Application received  9/25/2012