Case Summary | | | 1/31/2014 | | DONE |
|
|
|
|
Case Summary | | | 1/23/2014 | | DONE |
|
|
|
|
Miscellaneous action | | | 9/24/2013 | | DONE |
|
|
|
Documents scanned into Onbase and Tidemark
|
Plan resubmittals received | | | 5/31/2013 | | DONE |
Tisha Gallop
|
|
|
One copy (2 plan sheets) of as-builts provided by contractor, taken to Troy Cobbley
|
Meeting | | | 5/28/2013 | | DONE |
|
|
|
Had a meeting with Bruce of CM Company regarding as-built requirements for the 3rd floor. His specific question was with regard to the existing magnetic door holders that release upon general alarm. Previously, these devices were not shown on the plans. I explained that typically, door release functions after the fact would require a plan modification. However, under the circumstances that the door holders were part of the original system, just not shown on the plans, I verified that the door holders could be indicated on the as-built drawings. I explained that they would need to be shown on the floorplans, on the one-line, and in the I/O matrix. We discussed that a portion of the building remodel was to ensure we have an accurate record of the system. Therefore, this must be included in the as-built drawings and documentation.
|
Case Summary | | | 5/20/2013 | | DONE |
|
|
|
|
INSP-Final Inspection | 5/7/2013 | 5/9/2013 | 5/9/2013 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled. I need as-builts showing the added heat detector, new a/v and the interconnection to the existing door mags....ect.
|
Permit Ready to Issue | | | 5/3/2013 | | |
|
|
|
|
Inspection Record Card- Fire | 5/3/2013 | | 5/3/2013 | | DONE |
Darla L Downs
|
|
|
|
Telephone call | | | 5/3/2013 | | |
|
|
|
5-3-13 called Mike -Doherty Electric permit ready and fee given ///dld
|
CHANGE STATUS TO (ISS) | | | 5/3/2013 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 4/9/2013 | | 5/2/2013 | | DONE |
Stephanie L. Cobbley
|
|
|
Plan Modification
|
Alarm Plan Check | 5/2/2013 | | 5/2/2013 | | PASS |
Stephanie L. Cobbley
|
|
|
Plan modification resubmittal approved with redlines and review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 5/2/2013 | | DONE |
|
|
|
Approved plans taken to permit technician for processing.
|
Plan resubmittals received | | | 5/1/2013 | | |
|
|
|
5-1-13 received 1 application,2 files & 4 sheets/plans sent to SLC
|
Alarm Plan Check | 4/23/2013 | | 4/23/2013 | | FAIL |
Stephanie L. Cobbley
|
|
|
Plan modifications denied - many of the previous redlines have not been implemented, and floorplan layout changes discussed in the email have not been shown.
|
Miscellaneous action | | | 4/23/2013 | | DONE |
|
|
|
Faxed review comments to the applicant.
|
Miscellaneous action | | | 4/22/2013 | | DONE |
|
|
|
Applicant brought in revised plans, however they do not reflect any of the redlines or changes discussed.
|
Miscellaneous action | | | 4/16/2013 | | DONE |
|
|
|
Emailed the applicant because several redlines from the previous review were not implemented into the plan modification set. He emailed back stating that some of the redlines were implemented in the field but were not transferred to the drawings. He also forwarded an email from the contractor stating that some walls were incorrect and device locations and counts are incorrect. I explained to the applicant that I could not approved the plan modifications unless they match the installation. I let him know that I would not fail the plans yet but I would need revised drawings and calcs by Friday, 4/19/13.
|
Plan resubmittals received | | | 4/9/2013 | | DONE |
Tisha Gallop
|
|
|
Plan Modification: Received two copies of application, submittal folder and plans; routed to Fire Review.
|
INSP-Conference | 4/4/2013 | 4/5/2013 | 4/5/2013 | A | CANC |
Forrest France
|
|
|
Bruce CM co. phone #: ###-#### Inspection cancelled from web by: Shawna Gates
|
Telephone call | | | 3/19/2013 | | DONE |
|
|
|
Rob with Protex called. He stated that the following changes have been made:
1.Eliminate the (3) duct detectors in the council chambers
2.Add a relay module for lighting control in the council chambers
And wanted to know if a resubmittal required?
I let him know if those are the only modifications, then as-built drawings should cover it. I asked him to please ensure the original comments/redlines have been implemented and calcs/voltage drops revised, as well as updating the operations matrix. Subject to inspector approval.
|
FIR-Aging Inspection | 2/28/2013 | 2/28/2013 | 2/28/2013 | | DONE |
Forrest France
|
|
|
Work in progress
|
INSP-Alarm Testing | 11/13/2012 | 11/15/2012 | 11/14/2012 | A | CANC |
Troy Cobbley
|
|
|
We need to schedule a fire alarm test for the 1st main lobby and misc. offices at Boise city hall, we need to start at 7am. please call mike to confirm ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates Inspection cancelled from web by: Shawna Gates
|
Override - Parcel Holds | | | 10/9/2012 | | |
|
|
|
|
Issue and Print Permit | | | 10/9/2012 | | DONE |
Barbara Stitt
|
|
|
|
Plan assigned to (Stephanie) | 9/25/2012 | | 10/8/2012 | | DONE |
Stephanie L. Cobbley
|
|
|
|
1st review completed | | | 10/8/2012 | | PASS |
|
|
|
|
Alarm Plan Check | 10/8/2012 | | 10/8/2012 | | PASS |
Stephanie L. Cobbley
|
|
|
Plans approved with redlines and review comments - asbuilt drawings and documents required at time of final inspection
|
PLANS TAKEN FRONT DESK ALARM | | | 10/8/2012 | | DONE |
|
|
|
Approved redlined plans taken to permit technician for processing.
|
Override - Parcel Holds | | | 10/8/2012 | | |
|
|
|
|
Permit Ready to Issue | | | 10/8/2012 | | DONE |
Tisha Gallop
|
|
|
|
Override - Parcel Holds | | | 10/8/2012 | | |
|
|
|
|
Inspection Record Card- Fire | 10/8/2012 | | 10/8/2012 | | DONE |
Tisha Gallop
|
|
|
|
Override - Parcel Holds | | | 10/8/2012 | | |
|
|
|
|
Permit Ready to Issue | | | 10/8/2012 | | DONE |
Tisha Gallop
|
|
|
|
Telephone call | | | 10/8/2012 | | DONE |
Tisha Gallop
|
|
|
called Doherty Elec and told her permit is ready and fee.
|
Miscellaneous action | | | 10/5/2012 | | DONE |
|
|
|
Received room names/uses
|
Miscellaneous action | | | 10/4/2012 | | DONE |
|
|
|
Recieved an email with generic areas defined.
|
Meeting | | | 10/4/2012 | | DONE |
|
|
|
Had a brief meeting with R. Bousfeild and explained the detail I need for the room use. He stated that now that he knows what I need, he will get the information for me by tomorrow.
|
Telephone call | | | 10/2/2012 | | DONE |
|
|
|
Left a message for Chris Curtis requesting the room names and uses for the third floor.
|
Telephone call | | | 9/28/2012 | | DONE |
|
|
|
Chris with CH2MHill called. He stated the full area smoke detection is for fire/smoke damper shut down in case they get to the end of the project and found fire/smoke dampers. I expresed concern over providing detection when it is not certain that the f/s dampers even exist. I also expressed concern because the panel signal circuits are getting very full. He said they would just add another panel if needed. He has opted to stay with the submitted design of full area smoke detection for f/s damper shutdown. I requested an email or fax of the room names so I can verify room use for detection and notification purposes. He said he would get me the information right away.
|
Telephone call | | | 9/26/2012 | | DONE |
|
|
|
Left Bret w/CH2MHill a message to ask about the intended use of the non-required smoke detectors.
|
Meeting | | | 9/26/2012 | | DONE |
|
|
|
Met with Rob Bousfield to go over possible issues with non-required proposed smoke detecton maxing out the existing fire alarm panels
|
Application received | | | 9/25/2012 | | |
|
|
|
|