Permit Information
Permit NumberFIR12-00557
StatusFinaled
Name ALARM STAR
Site Address 1875 S CENTURY WAY
Project NameWINGS CENTER
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to replace an existing manual fire alarm system in an existing building. This system includes a pull station, smoke detector, notification, and sprinkler system monitoring. No HVAC is indicated on the plans.
Associated building permit: BLD11-03007
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  2/14/2013 DONE
Plans taken to records for scanning
INSP-Final Inspection1/17/20131/17/20131/17/2013PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Alarm Testing1/16/20131/16/20131/16/2013PFAIL
DetailsTroy Cobbley
Retested and sent signals but none were received at central station. All so still need map and as-builts.
INSP-Final Inspection1/15/20131/15/20131/16/2013PCANC
DetailsTroy Cobbley
To be canceled per Rand Phone #: ###-####
Override - Parcel Holds1/16/20131/1/19001/16/2013  
Fire alarm inspection
Override - Parcel Holds1/15/20131/1/19001/15/2013  
alarm final
INSP-Final Inspection1/14/20131/14/20131/14/2013PFAIL
DetailsTroy Cobbley
For todays inspection we verified strobe spacing in the high ceiling areas. At the east end of the building Rand and I agreed that relocating one strobe in the low ceiling area will provide coverage in another high ceiling area. That work was performed as I waited. The smoke detectors were tested as well. However no signals were received at the monitoring station. To final this project signals need to be received, as-builts provided, map at the facp.
INSP-Final Inspection1/11/20131/11/20131/11/2013PFAIL
DetailsTroy Cobbley
Todays inspection was just verification that the notification circuits and devices functioned.They were out of sync but were repaired. EOL voltage was verified as ok. Candellas were adjusted in several locations due to spacing issues. Spacing was verified on only the low ceiling areas. The high ceilings will need to be checked later. As-builts will be required showing the revised circuits and candellas and additional devices.
INSP-Sprinkler Rough-in12/24/201212/24/201212/24/2012PDONE
DetailsTroy Cobbley
rand and I went over smoke alarms in the daycare area and strobe coverage.
Override - Parcel Holds12/24/20121/1/190012/24/2012  
this is for fire inspection only
INSP-Final Inspection12/20/201212/21/201212/21/2012PCANC
DetailsForrest France
Rand Phone #: ###-####
INSP-Final Inspection12/20/201212/20/201212/20/2012PCANC
DetailsTroy Cobbley
Notice of NSF check received 12-20-12 for this permit///final inspection cancelled until payment is received - Rand Phone #: ###-####
Override - Parcel Holds12/20/20121/1/190012/20/2012  
fire final
Override - Parcel Holds12/20/20121/1/190012/20/2012  
not this permit
Override - Parcel Holds  12/3/2012  
Issue and Print Permit  12/3/2012 DONE
Plan assigned to (Stephanie)9/28/2012 11/29/2012 DONE
DetailsStephanie L. Cobbley
Alarm Plan Check11/29/2012 11/29/2012 PASS
DetailsStephanie L. Cobbley
Resubmittals approved with redlines and review comments.
PLANS TAKEN FRONT DESK ALARM  11/29/2012 DONE
Approved plans taken to permit technician for processing.
Permit Ready to Issue  11/29/2012  
Inspection Record Card- Fire11/29/2012 11/29/2012 DONE
DetailsDarla L Downs
Telephone call  11/29/2012  
11-29-12 called Alarm Star permit ready and fee given ///dld
Plan resubmittals received  11/21/2012  
received 2 sets of plans and 1 circuit configuration taken to Steph in fire ///dld
Plan resubmittals received  11/20/2012 DONE
DetailsTisha Gallop
received application and two copies of submittal documents and plans; routed to SLC
1st review completed  10/11/2012 FAIL
Alarm Plan Check10/11/2012 10/11/2012 FAIL
DetailsStephanie L. Cobbley
Plans denied - see redlines and review comments.
Application received  9/28/2012