Miscellaneous action | | | 9/24/2013 | | DONE |
|
|
|
Documents scanned into Onbase and Tidemark
|
INSP-Final Inspection | 7/10/2013 | 7/10/2013 | 7/10/2013 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
FIR-Aging Inspection | 6/27/2013 | 6/27/2013 | 6/28/2013 | | NR |
Troy Cobbley
|
|
|
waiting on the outcome of fir13-00257
|
FIR-Aging Inspection | 3/26/2013 | 3/26/2013 | 3/28/2013 | | NR |
Troy Cobbley
|
|
|
Project status has been forwarded to Scott for action
|
INSP-Final Inspection | 10/22/2012 | 10/23/2012 | 10/23/2012 | A | FAIL |
Troy Cobbley
|
|
|
The audilbe and visual fire alarm devices shall be syncronized as per NFPA 72, sections 18.4.2.5 and 18.5.4.3.2. (the new devices do not audibly sync with the existing devices) Also corrected as-builts are needed showing the candella changes.
|
Issue and Print Permit | | | 10/16/2012 | | DONE |
Tisha Gallop
|
|
|
|
Plan assigned to (Stephanie) | 10/2/2012 | | 10/15/2012 | | DONE |
Stephanie L. Cobbley
|
|
|
|
1st review completed | | | 10/15/2012 | | PASS |
|
|
|
|
Alarm Plan Check | 10/15/2012 | | 10/15/2012 | | PASS |
Stephanie L. Cobbley
|
|
|
Plans approved with redlines and review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 10/15/2012 | | DONE |
|
|
|
Approved redlined plans taken to permit technician for processing.
|
Telephone call | | | 10/15/2012 | | DONE |
Christina Prado
|
|
|
Called Charlie to advise permit is ready, also gave fees due
|
Inspection Record Card- Fire | 10/15/2012 | | 10/15/2012 | | DONE |
Christina Prado
|
|
|
|
Permit Ready to Issue | | | 10/15/2012 | | DONE |
Christina Prado
|
|
|
|
Application received | | | 10/2/2012 | | |
|
|
|
|