INSP-Final Inspection | 10/30/2012 | 10/31/2012 | 10/31/2012 | A | PASS |
Forrest France
|
|
|
Repairs and adjustments finished. Hood suppression systems operated correctly during inspection. Permit finaled.
|
INSP-Final Inspection | 10/29/2012 | 10/30/2012 | 10/30/2012 | A | FAIL |
Forrest France
|
|
|
Activation of the 3 gallon ansul hood system failed to shut down gas supply at the appliances. Hood suppression system at the back kitchen cook line operated correctly under test conditions.
|
INSP-Final Inspection | 10/25/2012 | 10/26/2012 | 10/26/2012 | A | DEFR |
Forrest France
|
|
|
Pending equipment, gas service.
|
Application received | | | 10/3/2012 | | |
|
|
|
|
Issue and Print Permit | | | 10/3/2012 | | DONE |
|
|
|
|