Miscellaneous action | | | 12/26/2012 | | DONE |
|
|
|
plans taken to records for scanning.
|
INSP-Final Inspection | 12/12/2012 | 12/13/2012 | 12/13/2012 | A | PASS |
Forrest France
|
|
|
Remainder of fire alarm work passed field testing. Tenant to post updated points map including the new duct detector as agreed.
|
INSP-Alarm Testing | 12/10/2012 | 12/10/2012 | 12/10/2012 | P | PART |
Forrest France
|
|
|
New notification appliance circut and power supply tested satisfactory. Duct detector not tested due to HVAC equipment work in progress.
|
INSP-Sprinkler Rough-in/Hydro | 12/7/2012 | 12/10/2012 | 12/10/2012 | A | PART |
Forrest France
|
|
|
|
Issue and Print Permit | | | 12/5/2012 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 10/15/2012 | | 12/4/2012 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Alarm Plan Check | 12/4/2012 | | 12/4/2012 | | PASS |
Stephanie L. Cobbley
|
|
|
Resubmittals approved with written review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 12/4/2012 | | DONE |
|
|
|
Approved plans taken to permit technician for processing.
|
Permit Ready to Issue | | | 12/4/2012 | | |
|
|
|
|
Inspection Record Card- Fire | 12/4/2012 | | 12/4/2012 | | DONE |
Darla L Downs
|
|
|
|
Telephone call | | | 12/4/2012 | | |
|
|
|
12-4-12 called Lea Electric Kirk Meyer left message permit ready and fee given ///dld
|
Plan resubmittals received | | | 11/27/2012 | | DONE |
Christina Prado
|
|
|
received two sets of applications, submittal documents and plans ;taken to Stephanie for review
|
1st review completed | | | 10/24/2012 | | FAIL |
|
|
|
|
Alarm Plan Check | 10/24/2012 | | 10/24/2012 | | FAIL |
Stephanie L. Cobbley
|
|
|
Plans denied - see redlines and review comments.
|
Miscellaneous action | | | 10/24/2012 | | DONE |
|
|
|
Faxed review comments to applicant
|
Miscellaneous action | | | 10/24/2012 | | DONE |
|
|
|
emailed R. Ahten per his request letting him know the plans have been denied.
|
Application received | | | 10/15/2012 | | |
|
|
|
|