Miscellaneous action | | | 12/3/2012 | | DONE |
|
|
|
Plans taken to records for scanning.
|
INSP-Final Inspection | 11/14/2012 | 11/14/2012 | 11/14/2012 | A | PASS |
Forrest France
|
|
|
Fire alarm work passed field inspection. Permit finaled.
|
INSP-Final Inspection | 11/13/2012 | 11/13/2012 | 11/13/2012 | P | CANC |
Troy Cobbley
|
|
|
Overbooked. Brian will reschedule for tomorrow
|
INSP-Alarm Testing | 11/13/2012 | 11/13/2012 | 11/13/2012 | P | CANC |
Troy Cobbley
|
|
|
Overbooked. Brian will reschedule for tomorrow
|
Telephone call | | | 11/9/2012 | | DONE |
|
|
|
Charlie with SimplexGrinnell called to ask about notification requirements in private restrooms. I confirmed that if it is a restroom off of a private office with no other access to it by general employees or the public, then notification would not be required. I agreed that an as-built drawing would suffice rather than submiting a plan modification.
|
INSP-Final Inspection | 11/8/2012 | 11/8/2012 | 11/8/2012 | P | NR |
Forrest France
|
|
|
Pending installation of a WP notification appliance at one location.
|
Inspection Record Card- Fire | 11/2/2012 | | 11/2/2012 | | DONE |
Tisha Gallop
|
|
|
|
Permit Ready to Issue | | | 11/2/2012 | | DONE |
Tisha Gallop
|
|
|
|
Telephone call | | | 11/2/2012 | | DONE |
Tisha Gallop
|
|
|
called Simplex and left vm in general mailbox that permit is ready and fee.
|
Issue and Print Permit | | | 11/2/2012 | | DONE |
Barbara Stitt
|
|
|
|
Plan assigned to (Stephanie) | 10/19/2012 | | 11/1/2012 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Telephone call | | | 11/1/2012 | | DONE |
|
|
|
Left a message for Charlie with SimplexGrinnell letting him know I have questions on the fire alarm.
|
Miscellaneous action | | | 11/1/2012 | | DONE |
|
|
|
Emailed Dante Frassa with SimplexGrinnell requesting the total Watts available. The calcs recieved only state how many are being used by the new devices.
|
1st review completed | | | 11/1/2012 | | PASS |
|
|
|
Plans approved pending available Wattage is provided.
|
Miscellaneous action | | | 11/1/2012 | | DONE |
|
|
|
Received requested information
|
Alarm Plan Check | 11/1/2012 | | 11/1/2012 | | PASS |
Stephanie L. Cobbley
|
|
|
Plans approved with review comments and ammended speaker load calculations
|
PLANS TAKEN FRONT DESK ALARM | | | 11/1/2012 | | DONE |
|
|
|
Approved plans taken to permit technician for processing.
|
Application received | | | 10/19/2012 | | |
|
|
|
|