Miscellaneous action | | | 4/8/2013 | | DONE |
Tim Frost
|
|
|
Sent to Records for scanning.
|
INSP-Final Inspection | 1/24/2013 | 1/25/2013 | 1/25/2013 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled. Bell has been relocated and tested.
|
INSP-Final Inspection | 1/23/2013 | 1/24/2013 | 1/24/2013 | A | FAIL |
Troy Cobbley
|
|
|
The outside alarm bell needs to be relocated to the front of the home. This was verified with Romeo. Once the bell has been retested the permit can be finaled.
|
INSP-Supply line flush | 1/23/2013 | 1/24/2013 | 1/24/2013 | A | PASS |
Troy Cobbley
|
|
|
Underground flush passed
|
INSP-Final Inspection | 1/22/2013 | 1/23/2013 | 1/23/2013 | P | CANC |
Troy Cobbley
|
|
|
Cancel per Robert since the water is not turned on yet.
|
INSP-Supply line flush | 1/22/2013 | 1/23/2013 | 1/23/2013 | P | CANC |
Troy Cobbley
|
|
|
Cancel per Robert since the water is not turned on yet.
|
INSP-Final Inspection | 1/16/2013 | 1/18/2013 | 1/18/2013 | A | CANC |
Forrest France
|
|
|
Roberts is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|
INSP-Supply line flush | 1/16/2013 | 1/18/2013 | 1/18/2013 | A | CANC |
Forrest France
|
|
|
This is an ug flush. Roberts is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|
Sprinkler Plan Check | 1/15/2013 | | 1/15/2013 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/15/2013 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 1/15/2013 | | 1/15/2013 | | DONE |
Christina Prado
|
|
|
|
(F) Reprint permit | | | 1/15/2013 | | DONE |
Christina Prado
|
|
|
|
CHANGE STATUS TO (ISS) | | | 1/15/2013 | | DONE |
Christina Prado
|
|
|
|
INSP-Sprinkler Rough-in | 12/7/2012 | 12/7/2012 | 12/7/2012 | P | PASS |
Troy Cobbley
|
|
|
The underground supply piping under the house has been attached to the underside of the floor joists as discussed.
|
INSP-Sprinkler Rough-in | 12/5/2012 | 12/5/2012 | 12/5/2012 | P | PASS |
Troy Cobbley
|
|
|
I met the builder, Garrett, on site and he made repairs that I needed. Piping can be covered.
|
INSP-Sprinkler Rough-in | 12/3/2012 | 12/4/2012 | 12/4/2012 | A | FAIL |
Troy Cobbley
|
|
|
This is a tenting inspection. The General Contractor is the contact. David Paul. Thanks Phone #: ###-####.
I left voice message for contact stating I was on the way to the project. I found some of the tenting repaired but other areas I found where the plastic tenting can easily be moved and is not secured. Also one vertical riser appears to need batt insulation to protect it if it extends above the blow-in insulation when installed. Piping still can not be covered.
|
INSP-Sprinkler Rough-in | 11/29/2012 | 11/30/2012 | 11/30/2012 | A | PART |
Troy Cobbley
|
|
|
The sprinkler piping can not be covered due to the tenting not being adequate in many locations. However the underground supply piping can now be buried.
|
INSP-Sprinkler Rough-in | 11/27/2012 | 11/27/2012 | 11/27/2012 | P | FAIL |
Troy Cobbley
|
|
|
Reinspect for the underground failed. No work to correct the bury depth has been performed.
|
INSP-Sprinkler Rough-in/Hydro | 11/21/2012 | 11/26/2012 | 11/26/2012 | A | PART |
Troy Cobbley
|
|
|
The overhead hydro test passed. The underground supply line still is not ok for cover due to the minimum depth not being met.
|
INSP-Sprinkler Rough-in/Hydro | 11/20/2012 | 11/21/2012 | 11/21/2012 | P | PART |
Troy Cobbley
|
|
|
The overhead hydro test failed due to a visable leak on the cpvc piping. The rough-in generaly passed except none of the tenting has been installed. Also the plans need to be resubmitted showing the 5 additional 90's between hydraulic node point 7 and 101. Also sprinkler coverage is required in the shower or a lintel of 8" as per our discussion. Piping can not be covered yet.
|
INSP-Sprinkler Rough-in/Hydro | 11/19/2012 | 11/21/2012 | 11/20/2012 | A | CANC |
Troy Cobbley
|
|
|
This is an ug&oh hydro and rough to cover inspection. Robert is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|
INSP-Sprinkler Rough-in | 11/19/2012 | 11/20/2012 | 11/20/2012 | A | FAIL |
Troy Cobbley
|
|
|
This was an ug to cover inspection which failed due to the piping not meeting the min. bury depth of 4'6".
|
INSP-Sprinkler Rough-in/Hydro | 11/19/2012 | 11/21/2012 | 11/19/2012 | A | CANC |
Troy Cobbley
|
|
|
This is an ug hydro. Robert is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|
INSP-Sprinkler Rough-in | 11/19/2012 | 11/20/2012 | 11/19/2012 | A | CANC |
Troy Cobbley
|
|
|
This is an ug to cover. Robert is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|
Issue and Print Permit | | | 11/13/2012 | | DONE |
Christina Prado
|
|
|
|
Plan assigned to (Tim) | 11/1/2012 | | 11/7/2012 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 11/7/2012 | | 11/7/2012 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 11/7/2012 | | PASS |
Tim Frost
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/7/2012 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 11/7/2012 | | 11/7/2012 | | DONE |
Tisha Gallop
|
|
|
|
Permit Ready to Issue | | | 11/7/2012 | | DONE |
Tisha Gallop
|
|
|
|
Telephone call | | | 11/7/2012 | | DONE |
Tisha Gallop
|
|
|
called Camron and told him permit is ready and fee.
|
Case Summary | | | 11/1/2012 | | DONE |
Barbara Stitt
|
|
|
|
Application received | | | 11/1/2012 | | DONE |
Barbara Stitt
|
|
|
|