Miscellaneous action | | | 3/6/2014 | | DONE |
Tim Frost
|
|
|
Sent to Records for scanning.
|
INSP-Final Inspection | 2/12/2014 | 2/13/2014 | 2/13/2014 | P | PASS |
Forrest France
|
|
|
Fire sprinkler permit finaled.
|
INSP-Final Inspection | 2/11/2014 | 2/12/2014 | 2/12/2014 | P | FAIL |
Forrest France
|
|
|
Missing trim and finishes at several locations, damaged SW head at the west stair 3rd floor, non-functional high/low air switch. Not ready for final.
|
INSP-Sprinkler Rough-in/Hydro | 2/3/2014 | 2/3/2014 | 2/3/2014 | A | PART |
Forrest France
|
|
|
OH hydrostatic test of the wet system completed and passed.
|
INSP-Sprinkler Rough-in/Hydro | 2/3/2014 | 2/3/2014 | 2/3/2014 | A | PART |
Forrest France
|
|
|
OH hydrostatic test of the new dry system passed.
|
INSP-Sprinkler Rough-in/Hydro | 1/31/2014 | 1/31/2014 | 1/31/2014 | P | NH |
Forrest France
|
|
|
PSI reduced prior to completion of test.
|
INSP-Sprinkler Rough-in/Hydro | 1/17/2014 | 1/21/2014 | 1/17/2014 | P | CANC |
Forrest France
|
|
|
Please call Colton 30 mins prior Phone #: ###-#### >> Inspection requested via web by Jacci Hunt Inspection cancelled from web by: Jacci Hunt
|
INSP-Sprinkler Rough-in/Hydro | 12/30/2013 | 12/30/2013 | 12/30/2013 | P | PART |
Forrest France
|
|
|
UG fire supply line hydrostatic test passed.
|
INSP-Sprinkler Rough-in/Hydro | 12/23/2013 | 12/23/2013 | 12/23/2013 | P | NR |
Forrest France
|
|
|
Incomplete work at the dry system, 1st and 2nd floor wet systems. UG fire supply line unable to maintain 200 psig.
|
INSP-Sprinkler Rough-in/Hydro | 12/12/2013 | 12/16/2013 | 12/17/2013 | P | PART |
Forrest France
|
|
|
Noted corrections at dry system, discussed OH and UG hydrostatic test schedule.
|
INSP-Supply line flush | 12/12/2013 | 12/16/2013 | 12/17/2013 | A | PART |
Forrest France
|
|
|
Please call Colton 30 mins prior Phone #: ###-#### >> Inspection requested via web by Jacci Hunt
|
CHANGE STATUS TO (ISS) | | | 12/11/2013 | | DONE |
Barbara Stitt
|
|
|
|
(F) Reprint permit | | | 12/11/2013 | | DONE |
Barbara Stitt
|
|
|
|
Plan assigned to (Tim) | 12/3/2013 | | 12/10/2013 | | DONE |
Tim Frost
|
|
|
|
Miscellaneous action | | | 12/10/2013 | | DONE |
|
|
|
Plan Mod #2 - 12/10/2013
Rcvd new hyd from Phoneix today 12/10/2013. The report is still wrong. I manually asjusted the hyd to the correct the problem. SInce they have a large enought cushion the hydraulics DO work.
|
Sprinkler Plan Check | 12/10/2013 | | 12/10/2013 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/10/2013 | | DONE |
Tim Frost
|
|
|
|
Telephone call | | | 12/10/2013 | | DONE |
|
|
|
Called Aaron to advise permit is ready and gave fees due
|
Permit Ready to Issue | | | 12/10/2013 | | DONE |
Christina Prado
|
|
|
|
Inspection Record Card- Fire | 12/10/2013 | | 12/10/2013 | | DONE |
Christina Prado
|
|
|
|
Plan resubmittals received | | | 12/3/2013 | | DONE |
Tisha Gallop
|
|
|
Plan Modification: Recieved three copies of application, submittal docs and plans; rotued to Fire
|
INSP-Sprinkler Rough-in | 11/25/2013 | 11/26/2013 | 11/26/2013 | A | FAIL |
Forrest France
|
|
|
Inspection for cover at the second floor (3rd level) failed due to installation not matching plans- calc area included. Provide plan modification for changes prior to approval for cover.
|
CHANGE STATUS TO (ISS) | | | 10/11/2013 | | DONE |
Tisha Gallop
|
|
|
picked up plan mod
|
Plan assigned to (Tim) | 10/4/2013 | | 10/10/2013 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 10/10/2013 | | 10/10/2013 | | FAIL |
Tim Frost
|
|
|
|
Miscellaneous action | | | 10/10/2013 | | DONE |
Tim Frost
|
|
|
Emailed contractor in regards to failed review.
|
Plan resubmittals received | | | 10/10/2013 | | |
|
|
|
received 3 sets of plans/application sent to Tim F.
|
Sprinkler Plan Check | 10/10/2013 | | 10/10/2013 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/10/2013 | | DONE |
Tim Frost
|
|
|
|
Telephone call | | | 10/10/2013 | | DONE |
Tisha Gallop
|
|
|
called Aaron and told him permit is ready and fee due.
|
Permit Ready to Issue | | | 10/10/2013 | | DONE |
Tisha Gallop
|
|
|
plan mod
|
Inspection Record Card- Fire | 10/10/2013 | | 10/10/2013 | | DONE |
Tisha Gallop
|
|
|
|
Plan resubmittals received | | | 10/4/2013 | | DONE |
Tisha Gallop
|
|
|
received three copies of application, submittal docs, and plans; routed to Tim F.
|
Plan resubmittals received | | | 10/2/2013 | | |
|
|
|
10-2-13 received 4 sets of plans sent to Tim F.
|
INSP-Sprinkler Rough-in | 9/18/2013 | 9/19/2013 | 9/23/2013 | A | NR |
Forrest France
|
|
|
|
INSP-Sprinkler Rough-in/Hydro | 9/20/2013 | 9/23/2013 | 9/23/2013 | A | NR |
Forrest France
|
|
|
Rough-in inspection at second floor incomplete due to changes in floorplan, main and branchline routing. Tie-ins at the east stairway unfinished. Need to provide stamped resubmittals reflecting actual pipe routing and accurate floorplan prior to approval for cover.
|
FIR-Aging Inspection | 4/4/2013 | 4/4/2013 | 4/5/2013 | | DONE |
Forrest France
|
|
|
Site construction in process
|
Plan assigned to (Tim) | 11/1/2012 | | 11/19/2012 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 11/19/2012 | | 11/19/2012 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/19/2012 | | DONE |
Tim Frost
|
|
|
|
Telephone call | | | 11/19/2012 | | DONE |
Christina Prado
|
|
|
Called Aaron to advise permit is ready and gave fees due
|
Inspection Record Card- Fire | 11/19/2012 | | 11/19/2012 | | DONE |
Christina Prado
|
|
|
|
Permit Ready to Issue | | | 11/19/2012 | | DONE |
Christina Prado
|
|
|
|
Issue and Print Permit | | | 11/19/2012 | | DONE |
Barbara Stitt
|
|
|
|
Plan resubmittals received | | | 11/13/2012 | | |
|
|
|
|
Sprinkler Plan Check | 11/7/2012 | | 11/7/2012 | | FAIL |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 11/7/2012 | | FAIL |
Tim Frost
|
|
|
|
Miscellaneous action | | | 11/7/2012 | | DONE |
|
|
|
Emailed contractor the review
|
CHANGE STATUS TO (REV) | | | 11/7/2012 | | |
|
|
|
|
Telephone call | | | 11/7/2012 | | |
|
|
|
11-7-12 called Phoenix Fire Protection-left message for Aaron permit ready for pick up ///dld
|
Application received | | | 11/1/2012 | | |
|
|
|
|