Miscellaneous action | | | 2/14/2013 | | DONE |
|
|
|
Plans taken to records for scanning
|
INSP-Final Inspection | 12/28/2012 | 12/31/2012 | 12/31/2012 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled. Music shuts off upon activation of alarm.
|
INSP-Final Inspection | 12/28/2012 | 12/28/2012 | 12/28/2012 | P | FAIL |
Troy Cobbley
|
|
|
The music did not shut down/reduce as required. THis is the last remaining item prior to a final sign offf.
|
INSP-Final Inspection | 12/17/2012 | 12/17/2012 | 12/18/2012 | P | PART |
Troy Cobbley
|
|
|
A temporary occupancy is being given with Scott Arellano's permission until the Arcade/music reduction/shutdown has been installed and tested. This approval is only for the kitchen area.
|
INSP-Alarm Testing | 12/12/2012 | 12/13/2012 | 12/13/2012 | P | DONE |
Troy Cobbley
|
|
|
Provide accurate as-builts, provide breaker locks, provide map at the facp, provide shutdown/reduction of music/arcade machines as per NFPA 72 18.4.1.5, 18.4.3.5, relocate smoke detector to the deck at the facp. Signals verified for flow and tamper switches, hvac reporting and shutdown and kitchen hood suppression systems. Spacing verified for audio/visual devices. EOL verified as ok.
|
Issue and Print Permit | | | 11/7/2012 | | DONE |
Barbara Stitt
|
|
|
|
Plan assigned to (Stephanie) | 11/1/2012 | | 11/6/2012 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Miscellaneous action | | | 11/6/2012 | | DONE |
|
|
|
Recieved an email from the owner's representative that they desire the non-required voice evacuation system.
|
1st review completed | | | 11/6/2012 | | PASS |
|
|
|
|
Alarm Plan Check | 11/6/2012 | | 11/6/2012 | | PASS |
Stephanie L. Cobbley
|
|
|
Plans approved with redlines and review comments - as-built drawings required at time of final inspection
|
PLANS TAKEN FRONT DESK ALARM | | | 11/6/2012 | | DONE |
|
|
|
Approved redlined plans taken to the permit technician for processing.
|
Inspection Record Card- Fire | 11/6/2012 | | 11/6/2012 | | DONE |
Alexandra L. DeYoung
|
|
|
|
Permit Ready to Issue | | | 11/6/2012 | | DONE |
|
|
|
|
Miscellaneous action | | | 11/5/2012 | | DONE |
|
|
|
Emailed the applicant to ask for direction. The plans indicate a voice evacuation system is required, however the building review has not been completed and indicates a voice evacuation system is not required. I asked the applicant to either 1)acknowlege the plans will be denied until the building review is complete, or 2) obtain a letter from the owner stating they want the voice evacuation system regardless of the occupant load.
|
Application received | | | 11/1/2012 | | |
|
|
|
|