Permit Information
Permit NumberFIR12-00640
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 546 N MILWAUKEE ST
Project NameDAVE & BUSTERS
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to replace the existing sprinkler monitoring system panel with a new panel with a new remote power supply. A required manual system is being provided with non-required voice evacuation. This permit scope of work includes monitoring existing sprinkler system valves, monitoring/shutdown of existing HVAC, provide new smoke detectors above the new panels, a new pull station in the existing riser room, a new remote annunciator panel, kitchen hood monitoring, and full coverage notification.
Associated building permit: BLD12-01461
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  2/14/2013 DONE
Plans taken to records for scanning
INSP-Final Inspection12/28/201212/31/201212/31/2012APASS
DetailsTroy Cobbley
Permit finaled. Music shuts off upon activation of alarm.
INSP-Final Inspection12/28/201212/28/201212/28/2012PFAIL
DetailsTroy Cobbley
The music did not shut down/reduce as required. THis is the last remaining item prior to a final sign offf.
INSP-Final Inspection12/17/201212/17/201212/18/2012PPART
DetailsTroy Cobbley
A temporary occupancy is being given with Scott Arellano's permission until the Arcade/music reduction/shutdown has been installed and tested. This approval is only for the kitchen area.
INSP-Alarm Testing12/12/201212/13/201212/13/2012PDONE
DetailsTroy Cobbley
Provide accurate as-builts, provide breaker locks, provide map at the facp, provide shutdown/reduction of music/arcade machines as per NFPA 72 18.4.1.5, 18.4.3.5, relocate smoke detector to the deck at the facp. Signals verified for flow and tamper switches, hvac reporting and shutdown and kitchen hood suppression systems. Spacing verified for audio/visual devices. EOL verified as ok.
Issue and Print Permit  11/7/2012 DONE
DetailsBarbara Stitt
Plan assigned to (Stephanie)11/1/2012 11/6/2012 DONE
DetailsStephanie L. Cobbley
Miscellaneous action  11/6/2012 DONE
Recieved an email from the owner's representative that they desire the non-required voice evacuation system.
1st review completed  11/6/2012 PASS
Alarm Plan Check11/6/2012 11/6/2012 PASS
DetailsStephanie L. Cobbley
Plans approved with redlines and review comments - as-built drawings required at time of final inspection
PLANS TAKEN FRONT DESK ALARM  11/6/2012 DONE
Approved redlined plans taken to the permit technician for processing.
Inspection Record Card- Fire11/6/2012 11/6/2012 DONE
DetailsAlexandra L. DeYoung
Permit Ready to Issue  11/6/2012 DONE
Miscellaneous action  11/5/2012 DONE
Emailed the applicant to ask for direction. The plans indicate a voice evacuation system is required, however the building review has not been completed and indicates a voice evacuation system is not required. I asked the applicant to either 1)acknowlege the plans will be denied until the building review is complete, or 2) obtain a letter from the owner stating they want the voice evacuation system regardless of the occupant load.
Application received  11/1/2012