Permit Information
Permit NumberFIR12-00644
StatusFinaled
Name ALARMCO
Site Address 2108 S CENTURY WAY
Project NameQuality Thermistor
Customer Number 
ePlanReviewNo
Description
12/18/12 Plan Modification (no initiating devices affected): This plan modification is to replace the DACT with an IGSMCF digital cellular communicator. New notes regarding this modification are at the end of the review comments starting on page 7.
This fire alarm permit is to replace the existing ADT fire alarm panel and system with new. This permit scope of work includes sprinkler system monitoring, duct detector monitoring for HVAC shutdown, a remote annunciator panel at the main entrance, a smoke detector above the FACP, a manual pull station in the riser room, and two voluntary heat detectors in the oven room. There is no associated building permit. The DACT is being replaced with an IPGSM-DP fire alarm communicator with cellular backup.
12/5/12: The contractor resubmitted with using the onboard DACT rather than a different communications technology.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  2/14/2013 DONE
Plans taken to records for scanning
INSP-Final Inspection1/28/20131/28/20131/28/2013APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection1/15/20131/16/20131/16/2013PFAIL
DetailsTroy Cobbley
Need a report of the signals sent today, as-builts showing the actual wiring of the dialer to the facp and verification sent to plan review to approve this wiring, and the duct smoke detectors repaired. Need signage on the facp room door as well.
Fees Due Hold12/20/2012 12/20/2012 DONE
DetailsChristina Prado
CHANGE STATUS TO (ISS)  12/19/2012 DONE
Plan assigned to (Stephanie)12/10/2012 12/18/2012 DONE
DetailsStephanie L. Cobbley
Alarm Plan Check12/18/2012 12/18/2012 PASS
DetailsStephanie L. Cobbley
plan modification approved.
PLANS TAKEN FRONT DESK ALARM  12/18/2012 DONE
Approved plan modification documents taken to the permit technician for processing.
Inspection Record Card- Fire12/18/2012 12/18/2012 DONE
DetailsDarla L Downs
Permit Ready to Issue  12/18/2012  
Telephone call  12/18/2012  
12-18-12 called Alarmco - Jason permit ready and fee given ///dld
Plan resubmittals received  12/10/2012 DONE
plan mod rec'd
Alarm Plan Check12/5/2012 12/5/2012 PASS
DetailsStephanie L. Cobbley
Plans approved with review comments.
PLANS TAKEN FRONT DESK ALARM  12/5/2012 DONE
Approved resubmittals taken to permit technician for processing.
Permit Ready to Issue  12/5/2012  
Inspection Record Card- Fire12/5/2012 12/5/2012 DONE
DetailsDarla L Downs
Telephone call  12/5/2012  
12-5-12 called Alarmco permit ready and fee given ///dld
Issue and Print Permit  12/5/2012 DONE
Plan assigned to (Stephanie)11/2/2012 12/5/2012 DONE
DetailsStephanie L. Cobbley
Plan resubmittals received  11/28/2012 DONE
DetailsChristina Prado
Received two sets of revised plans and documentation; gave to Stephanie for further review
1st review completed  11/13/2012 FAIL
Alarm Plan Check11/13/2012 11/13/2012 FAIL
DetailsStephanie L. Cobbley
Plans denied - see review comments and redlines
Miscellaneous action  11/13/2012 DONE
Emailed contractor to let them know the plans are being denied.
Miscellaneous action  11/13/2012 DONE
Faxed review comments to applicant
Miscellaneous action  11/13/2012 DONE
Plans placed in drawer at permit counter for contractor to pick up.
Telephone call  11/6/2012 DONE
Spoke to Alarmco regarding discrepencies in the information provided. This is a new communications technology not previously submitted to the City of Boise. I asked for an installation manual and clarification on items shown on the plans. The plans indicate internet communications with a land-line phone backup, however Alarmco stated during the phone conversation that it is wireless (similar to the AES radio) with a cell phone backup. I let them know that normally the process is to provide all information for a new communications method prior to using them in a fire alarm submital. I explained that I want time to go through the information thoroughly to determine if it is going to be allowed in our jurisdiction, to prepare adequate instruction for the inspectors, and to be able to review the plans accordingly. They said they would work on getting me the information I need.
Application received  11/2/2012 DONE
DetailsBarbara Stitt