Miscellaneous action | | | 2/14/2013 | | DONE |
|
|
|
Plans taken to records for scanning
|
INSP-Final Inspection | 1/7/2013 | 1/7/2013 | 1/7/2013 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
Plan assigned to (Stephanie) | 1/2/2013 | | 1/3/2013 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Telephone call | | | 1/3/2013 | | DONE |
|
|
|
Spoke to Jeff at Crane Alarm regarding the batteries for the AES panel. I explained that the previous documents had been redlined becuase they show 7ah batteries, however a minimum of 7.5ah is required. I asked him to verify what batteries were installed and to please email me with what that was as well as a data sheet for the installed batteries.
|
Miscellaneous action | | | 1/3/2013 | | DONE |
|
|
|
Received requested documentation.
|
Alarm Plan Check | 1/3/2013 | | 1/3/2013 | | PASS |
Stephanie L. Cobbley
|
|
|
2nd Plan modification approved with redlines and review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 1/3/2013 | | DONE |
|
|
|
Approved redlined plan modification documents taken to permit technician for processing.
|
Inspection Record Card- Fire | 1/3/2013 | | 1/3/2013 | | DONE |
Barbara Stitt
|
|
|
|
Inspection Record Card- Fire | 1/3/2013 | | 1/3/2013 | | DONE |
Barbara Stitt
|
|
|
|
Telephone call | | | 1/3/2013 | | DONE |
Barbara Stitt
|
|
|
Called Jeff and told him that permit is ready & fees due on 1-3-13 @ 11:10am//BAS
|
Permit Ready to Issue | | | 1/3/2013 | | DONE |
Barbara Stitt
|
|
|
|
(F) Reprint permit | | | 1/3/2013 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 1/3/2013 | | |
|
|
|
|
Plan resubmittals received | | | 1/2/2013 | | |
|
|
|
Plan modification
|
INSP-Final Inspection | 12/31/2012 | 12/31/2012 | 12/31/2012 | P | FAIL |
Troy Cobbley
|
|
|
Plan modifications need to be submitted showing the actual wall layout, new devices/deleted devices and new circuits. Also include the correct model of duct smoke detectors used on the hvac units. I also will need the breaker identified and locked out, building map posted and NFPA 72 forms.
|
INSP-Final Inspection | 12/28/2012 | 12/28/2012 | 12/28/2012 | P | FAIL |
Troy Cobbley
|
|
|
Project is not ready for inspection. The system had not been turned on or pre-tested prior to inspection. I performed a walk around and noted on the city approved plans located where strobes are over spaced, have been added or deleted. It appears that strobes to the east of column line 8 will be blocked by racking that exceeds 6' in height. We did set off the audio/visuals after activating the panel and I found that neither the audio or visuals are sync'd. Per the fire alarm plans examiner due to small safety factor for the EOL voltages any changes will require a plan modification. Per Romeo it will be ok for the owner to stock if the fire alarm is inspected to verify that sprinkler and hvac monitoring is in place.
|
Alarm Plan Check | 12/27/2012 | | 12/27/2012 | | PASS |
Stephanie L. Cobbley
|
|
|
Plan modification approved with redlines and review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 12/27/2012 | | DONE |
|
|
|
Approved redlined plan modification documents taken to permit technician for processing.
|
Permit Ready to Issue | | | 12/27/2012 | | DONE |
Tisha Gallop
|
|
|
|
Inspection Record Card- Fire | 12/27/2012 | | 12/27/2012 | | DONE |
Tisha Gallop
|
|
|
|
Telephone call | | | 12/27/2012 | | DONE |
Tisha Gallop
|
|
|
called Jeff and told him plan mod is ready and fee
|
CHANGE STATUS TO (ISS) | | | 12/27/2012 | | DONE |
Barbara Stitt
|
|
|
|
(F) Reprint permit | | | 12/27/2012 | | DONE |
Barbara Stitt
|
|
|
|
Issue and Print Permit | | | 12/5/2012 | | DONE |
Barbara Stitt
|
|
|
|
Plan assigned to (Stephanie) | 11/14/2012 | | 11/28/2012 | | DONE |
Stephanie L. Cobbley
|
|
|
|
1st review completed | | | 11/28/2012 | | PASS |
|
|
|
|
Alarm Plan Check | 11/28/2012 | | 11/28/2012 | | PASS |
Stephanie L. Cobbley
|
|
|
Plans approved with redlines and review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 11/28/2012 | | DONE |
|
|
|
Approved plans taken to permit technician for processing.
|
Inspection Record Card- Fire | 11/28/2012 | | 11/28/2012 | | DONE |
Tisha Gallop
|
|
|
|
Permit Ready to Issue | | | 11/28/2012 | | DONE |
|
|
|
|
Telephone call | | | 11/28/2012 | | DONE |
Tisha Gallop
|
|
|
called Jeff/Crane Alarm and left message permit is ready and fee.
|
Application received | | | 11/13/2012 | | |
|
|
|
|
Case Summary | | | 11/13/2012 | | DONE |
|
|
|
|