Permit Information
Permit NumberFIR12-00670
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 4120 N EAGLE RD
Project NameBioLife Plasma Services
Customer Number 
ePlanReviewYes
Description
The fire sprinkler scope of work consists of protecting a new single story building. New 6”x 203± C-900 piping will supply a 4” riser with a 4” wall piv, 4” backflow preventer and 4” riser manifold. The 4” feed main supplies a tree type system with 2½” & 3” cross-mains and 1¼” branch lines. The majority of the building is light hazard except for the receiving area, which was designed for ordinary hazard II. The building is framed with steel beams and bar joist.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/28/20137/1/20137/1/2013APASS
DetailsTroy Cobbley
Permit finaled
INSP-Sprinkler Rough-in/Hydro6/27/20136/28/20136/28/2013PPASS
DetailsTroy Cobbley
Overhead hydro test passed.
INSP-Sprinkler Rough-in4/30/20135/1/20135/1/2013APASS
DetailsTroy Cobbley
All piping can be covered except the south "east/west" corridor and southeast room. Head installation is not complete in these two areas. Also additional sprinkler coverage will be required in the "electrical room" due to a half ceiling being installed. Also two additional dry pendants will be required behind the condensor units in the cooler.
INSP-Sprinkler Rough-in/Hydro4/29/20135/1/20134/30/2013PCANC
DetailsTroy Cobbley
Robert is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
INSP-Sprinkler Rough-in4/22/20134/23/20134/23/2013APASS
DetailsTroy Cobbley
See the city approved plans for locations where ceiling tile can be installed to cover piping
INSP-Sprinkler Rough-in3/28/20134/1/20134/1/2013PPASS
DetailsTroy Cobbley
See the city approved plans for two locations marked in red where the hardlid ceilings can be installed. Also the rough-in inspection for the overhead lines passed. Not all of the drops have been installed/piped. I noted two locations where retaining straps are not bent over the truss. Also plan modifications will be needed due to additional elbows in both the 2 1/2" and 4" mains that supply the remote areas.
INSP-Sprinkler Rough-in/Hydro3/28/20133/29/20133/29/2013ANR
DetailsForrest France
Robert is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus
INSP-Supply line flush3/28/20133/28/20133/28/2013PPASS
DetailsTroy Cobbley
Underground flush passed
INSP-Sprinkler Rough-in/Hydro3/27/20133/28/20133/28/2013PCANC
DetailsTroy Cobbley
Robert is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
INSP-Supply line flush3/27/20133/28/20133/28/2013ACANC
DetailsTroy Cobbley
Robert is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
INSP-Sprinkler Rough-in/Hydro3/20/20133/22/20133/22/2013APASS
DetailsTroy Cobbley
Underground hydro test passed
INSP-Supply line flush3/18/20133/22/20133/20/2013PCANC
DetailsTroy Cobbley
Robert is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
INSP-Sprinkler Rough-in/Hydro3/18/20133/22/20133/20/2013PCANC
DetailsTroy Cobbley
This is an ug hydro. Robert is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
INSP-Sprinkler Rough-in12/7/201212/10/201212/10/2012APART
DetailsTroy Cobbley
The underground supply line piping is ok to cover from the building to the blow off cap. The connection to United Water is not complete at this time due to bury depth. issues.
Plan assigned to (Tim)11/15/2012 12/4/2012 DONE
DetailsTim Frost
Sprinkler Plan Check12/4/2012 12/4/2012 PASS
DetailsTim Frost
Please, see attached comments.
There are NO annotations on the plans.
PLANS/APPL TAKEN TO FRONT DESK  12/4/2012 DONE
DetailsTim Frost
Inspection Record Card- Fire12/4/2012 12/4/2012 DONE
DetailsDarla L Downs
Inspection Record Card- Fire12/4/2012 12/4/2012 DONE
DetailsDarla L Downs
Issue and Print Permit  12/4/2012 DONE
Sprinkler Plan Check11/20/2012 11/20/2012 FAIL
DetailsTim Frost
Please, see attached comments.
There are NO annotations on the plans.
1st review completed  11/20/2012 FAIL
DetailsTim Frost
Miscellaneous action  11/20/2012 DONE
DetailsTim Frost
Emailed review to contractor
Telephone call  11/20/2012  
11-20-12 called Shilo Automatic Sprinkler -Tom permit needs to be picked up ///dld
Application received  11/15/2012  
Case Summary  11/15/2012 DONE
DetailsBarbara Stitt