Miscellaneous action | | | 2/14/2013 | | DONE |
|
|
|
Plans taken to records for scanning
|
INSP-Final Inspection | 1/17/2013 | 1/18/2013 | 1/18/2013 | A | PASS |
Forrest France
|
|
|
Knox box to be installed prior to building permit final. Acceptance testing passed.
|
Alarm Plan Check | 1/16/2013 | | 1/16/2013 | | PASS |
Stephanie L. Cobbley
|
|
|
resubmitted plan modification approved with redlines and review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 1/16/2013 | | DONE |
|
|
|
approved plan modification documents taken to permit technician for processing.
|
Inspection Record Card- Fire | 1/16/2013 | | 1/16/2013 | | DONE |
Darla L Downs
|
|
|
|
Permit Ready to Issue | | | 1/16/2013 | | |
|
|
|
|
Telephone call | | | 1/16/2013 | | |
|
|
|
1-16-13 called Brian- Local Fire and Security permit ready and fee given ///dld
|
CHANGE STATUS TO (ISS) | | | 1/16/2013 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 1/3/2013 | | 1/16/2013 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Plan resubmittals received | | | 1/10/2013 | | |
|
|
|
1-9-13 received 2 applications,fire alarm submittal checklist & 2 sets of plan mod resubmittals sent to SLC
|
Miscellaneous action | | | 1/9/2013 | | DONE |
|
|
|
Received requested letter from the manufacturer
|
Telephone call | | | 1/8/2013 | | DONE |
|
|
|
Spoke to Brian regarding the DSC 3G3070CF communicator he submitted. I explained that I have never seen this partcular communicator before and that typically I do not allow new communications methods to be part of a fire alarm submittal. He explained that it is the same as the 3055 (previously approved for use) only it uses 3G instead of 2G. I let him know that if he could get something from the company in writing that states that, as well as an installation manual, that I would go ahead and review it in this case. He said he would get the information to me today.
|
Alarm Plan Check | 1/8/2013 | | 1/8/2013 | | FAIL |
Stephanie L. Cobbley
|
|
|
Plan modification denied - see review comments - no new redlines, please see previous redlines from original review.
|
Telephone call | | | 1/8/2013 | | DONE |
|
|
|
Spoke to Brian to let him know that none of the notification is shown on the plan modification, so I need to reject the plans. I let him know that the plan modification must be able to completely replace the previous plans, including incorporating the previous redlines.
|
Miscellaneous action | | | 1/8/2013 | | DONE |
|
|
|
Received the installation manual. Still waiting for the letter from the manufacturer.
|
Miscellaneous action | | | 1/8/2013 | | DONE |
|
|
|
Emailed Brian (no fax number provided) letting him know the plans have been denied and can be picked up from the permit technician.
|
Plan resubmittals received | | | 1/3/2013 | | |
|
|
|
PLan modification
|
INSP-Conference | 12/10/2012 | 12/11/2012 | 12/11/2012 | A | DONE |
Troy Cobbley
|
|
|
Brian and I went over audio/visual device placement/spacing issues and smoke detector placement in the exit corridors.
|
Telephone call | | | 12/10/2012 | | DONE |
|
|
|
Brian with Local Fire & Security called. He said that the ceilings may be too low to mount the horn/strobes and strobe only devices at the minimum height of 80 inches. I let him know that NFPA 72 has allowances for lower ceiling heights, but he may have to increase candela ratings. I refered him to NFPA 72 18.5.4.2 and explained there would be some calculations involved in determining what the new candela rating would need to be if he can't mount them at the 80 inch minimum.
|
Issue and Print Permit | | | 12/6/2012 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 11/19/2012 | | 12/4/2012 | | DONE |
Stephanie L. Cobbley
|
|
|
|
1st review completed | | | 12/4/2012 | | PASS |
|
|
|
|
Alarm Plan Check | 12/4/2012 | | 12/4/2012 | | PASS |
Stephanie L. Cobbley
|
|
|
Plans approved with redlines and review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 12/4/2012 | | DONE |
|
|
|
Approved plans taken to permit technician for processing.
|
Permit Ready to Issue | | | 12/4/2012 | | |
|
|
|
|
Inspection Record Card- Fire | 12/4/2012 | | 12/4/2012 | | DONE |
Darla L Downs
|
|
|
|
Telephone call | | | 12/4/2012 | | |
|
|
|
12-4-12 called Local Fire and Security Brian Hodge- permit ready and fee given ///dld
|
Application received | | | 11/19/2012 | | |
|
|
|
|