Permit Information
Permit NumberFIR12-00675
StatusFinaled
Name LOCAL FIRE AND SECURITY
Site Address 8050 W USTICK RD
Project NameRising Sun
Customer Number 
ePlanReviewNo
Description
1/16/13 Resubmitted Plan Modification (no initiating devices affected): This plan modification is to replace the DACT with a DSC wireless communicator (please see additional notes beginning on page 6 of this review) and to incorporate previous redlines and review comments.
1/8/13 Plan Modification (no initiating devices affected): This plan modification is to replace the DACT with a DSC wireless communicator. Please see additional notes beginning on page 6 of this review.
12/4/12: This fire alarm permit is to replace the existing fire alarm system with a new manual system. This permit scope of work includes pull stations at every exit, a smoke detector above the FACP, notification, system smoke detectors programmed for supervisory in place of single/multi-station smoke alarms, and a remote power supply. The initiating devices are wireless.
Associated building permit: BLD12-01984
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  2/14/2013 DONE
Plans taken to records for scanning
INSP-Final Inspection1/17/20131/18/20131/18/2013APASS
DetailsForrest France
Knox box to be installed prior to building permit final. Acceptance testing passed.
Alarm Plan Check1/16/2013 1/16/2013 PASS
DetailsStephanie L. Cobbley
resubmitted plan modification approved with redlines and review comments.
PLANS TAKEN FRONT DESK ALARM  1/16/2013 DONE
approved plan modification documents taken to permit technician for processing.
Inspection Record Card- Fire1/16/2013 1/16/2013 DONE
DetailsDarla L Downs
Permit Ready to Issue  1/16/2013  
Telephone call  1/16/2013  
1-16-13 called Brian- Local Fire and Security permit ready and fee given ///dld
CHANGE STATUS TO (ISS)  1/16/2013 DONE
Plan assigned to (Stephanie)1/3/2013 1/16/2013 DONE
DetailsStephanie L. Cobbley
Plan resubmittals received  1/10/2013  
1-9-13 received 2 applications,fire alarm submittal checklist & 2 sets of plan mod resubmittals sent to SLC
Miscellaneous action  1/9/2013 DONE
Received requested letter from the manufacturer
Telephone call  1/8/2013 DONE
Spoke to Brian regarding the DSC 3G3070CF communicator he submitted. I explained that I have never seen this partcular communicator before and that typically I do not allow new communications methods to be part of a fire alarm submittal. He explained that it is the same as the 3055 (previously approved for use) only it uses 3G instead of 2G. I let him know that if he could get something from the company in writing that states that, as well as an installation manual, that I would go ahead and review it in this case. He said he would get the information to me today.
Alarm Plan Check1/8/2013 1/8/2013 FAIL
DetailsStephanie L. Cobbley
Plan modification denied - see review comments - no new redlines, please see previous redlines from original review.
Telephone call  1/8/2013 DONE
Spoke to Brian to let him know that none of the notification is shown on the plan modification, so I need to reject the plans. I let him know that the plan modification must be able to completely replace the previous plans, including incorporating the previous redlines.
Miscellaneous action  1/8/2013 DONE
Received the installation manual. Still waiting for the letter from the manufacturer.
Miscellaneous action  1/8/2013 DONE
Emailed Brian (no fax number provided) letting him know the plans have been denied and can be picked up from the permit technician.
Plan resubmittals received  1/3/2013  
PLan modification
INSP-Conference12/10/201212/11/201212/11/2012ADONE
DetailsTroy Cobbley
Brian and I went over audio/visual device placement/spacing issues and smoke detector placement in the exit corridors.
Telephone call  12/10/2012 DONE
Brian with Local Fire & Security called. He said that the ceilings may be too low to mount the horn/strobes and strobe only devices at the minimum height of 80 inches. I let him know that NFPA 72 has allowances for lower ceiling heights, but he may have to increase candela ratings. I refered him to NFPA 72 18.5.4.2 and explained there would be some calculations involved in determining what the new candela rating would need to be if he can't mount them at the 80 inch minimum.
Issue and Print Permit  12/6/2012 DONE
Plan assigned to (Stephanie)11/19/2012 12/4/2012 DONE
DetailsStephanie L. Cobbley
1st review completed  12/4/2012 PASS
Alarm Plan Check12/4/2012 12/4/2012 PASS
DetailsStephanie L. Cobbley
Plans approved with redlines and review comments.
PLANS TAKEN FRONT DESK ALARM  12/4/2012 DONE
Approved plans taken to permit technician for processing.
Permit Ready to Issue  12/4/2012  
Inspection Record Card- Fire12/4/2012 12/4/2012 DONE
DetailsDarla L Downs
Telephone call  12/4/2012  
12-4-12 called Local Fire and Security Brian Hodge- permit ready and fee given ///dld
Application received  11/19/2012