INSP-Final Inspection | 12/17/2013 | 12/17/2013 | 12/18/2013 | P | PASS |
Forrest France
|
|
|
|
INSP-Final Inspection | 12/12/2013 | 12/13/2013 | 12/13/2013 | A | PART |
Forrest France
|
|
|
C/N items include matched temp heads at an electrical room, replace hanger on added coverage, access to NW elevator machine room, floor drain function at the fire pump room.
|
INSP-Final Inspection | 11/27/2013 | 12/2/2013 | 12/3/2013 | A | PART |
Forrest France
|
|
|
Need to remove valves in the pressure sensing lines per NFPA 20, pump room still missing ventilation, floor drain does not function, final walkthrough at the basement incomplete.
|
INSP-Final Inspection | 11/19/2013 | 11/22/2013 | 11/26/2013 | A | NR |
Forrest France
|
|
|
Mike B is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus
|
Sprinkler Plan Check | 11/20/2013 | | 11/20/2013 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/20/2013 | | DONE |
Tim Frost
|
|
|
|
CHANGE STATUS TO (ISS) | | | 11/20/2013 | | DONE |
Christina Prado
|
|
|
|
(F) Reprint permit | | | 11/20/2013 | | DONE |
Christina Prado
|
|
|
|
Plan resubmittals received | | | 11/18/2013 | | DONE |
|
|
|
Pump Room plan modification received.
|
Miscellaneous action | | | 11/15/2013 | | DONE |
|
|
|
Sent email to Jim Darr
Jim,
I need a revised drawing showing the new fire pump room. Apparently it is finished. Did any sprinkler have to be relocated?
|
INSP-Sprinkler Rough-in | 10/8/2013 | 10/10/2013 | 10/10/2013 | A | PART |
Forrest France
|
|
|
Completed fire pump acceptance testing per NFPA 20. Noted fire pump room is missing required ventilation, floor drain does not function adequately, upright heads at the new west wall exceed min. distance from the wall.
|
Miscellaneous action | | | 9/26/2013 | | DONE |
|
|
|
Email to architect Jason Butler
Per my previous review, various letters and conversation, it was discussed that the fire pump room at 8th and main does not comply with NFPA 20. I understood that the fire pump room was to be isolated per NFPA 20 requirements. The changes will of course be required BEFORE any occupancy is permitted. The sprinklers in this area may need to be revised due to the new wall configuration. What is the status of making these changes to the fire pump room?
|
INSP-Sprinkler Rough-in/Hydro | 3/27/2013 | 3/29/2013 | 3/29/2013 | P | PART |
Forrest France
|
|
|
For overhead hydrostatic testing of the header and supply piping.
|
INSP-Sprinkler Rough-in | 2/26/2013 | 2/27/2013 | 3/1/2013 | P | PART |
Forrest France
|
|
|
Noted corrections at the basement level shell work only.
|
Issue and Print Permit | | | 12/6/2012 | | DONE |
|
|
|
uploaded copy of permit into project dox
|
Issue and Print Permit | | | 12/5/2012 | | DONE |
Barbara Stitt
|
|
|
|
Inspection Record Card- Fire | 12/5/2012 | | 12/5/2012 | | DONE |
Barbara Stitt
|
|
|
|
Issue and Print Permit | | | 12/5/2012 | | DONE |
Barbara Stitt
|
|
|
|
Inspection Record Card- Fire | 12/5/2012 | | 12/5/2012 | | DONE |
Barbara Stitt
|
|
|
|
Plan assigned to (Tim) | 11/26/2012 | | 12/4/2012 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 12/4/2012 | | 12/4/2012 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/4/2012 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 11/29/2012 | | 11/29/2012 | | FAIL |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 11/29/2012 | | FAIL |
Tim Frost
|
|
|
|
Telephone call | | | 11/29/2012 | | |
|
|
|
11-29-12 called Shilo Automatic Sprinkler permit needs picked up ///dld
|
Application received | | | 11/26/2012 | | DONE |
Barbara Stitt
|
|
|
|