Permit Information
Permit NumberFIR12-00693
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 2014 S POND ST
Project NameHillcrest Courtyards
Customer Number 
ePlanReviewNo
Description
The fire sprinkler scope of work consists of protecting (5) one story town houses. Each town house has a dedicated 2” underground supply to a 1¼” back flow preventer. The system utilizes CPVC piping and extended coverage residential sprinklers. The piping will be tented in the attic to prevent freezing.

The underground is under permit FIR12-00583

FIELD INSPECTOR: The two-sprinkler rooms are based on 18’x18’ spacing. The one-sprinkler rooms are based on 20’x20’ spacing.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  9/23/2013 DONE
DetailsTim Frost
Sent to Records for scanning.
INSP-Final Inspection5/21/20135/21/20135/21/2013PPASS
DetailsTroy Cobbley
Permit finaled. Bells have been relocated and function correctly
INSP-Final Inspection5/20/20135/21/20135/21/2013AFAIL
DetailsTroy Cobbley
Need the light fixture installed between the two pendant heads in the entry from the garage.
INSP-Conference5/20/20135/20/20135/20/2013PDONE
DetailsTroy Cobbley
Frank and I discussed the relocation of the electric alarm bells to the nearest point ot the building to the street. Per Potter Electric the bell must be mounted vertical with the weather proof back boxes (per NEC).
INSP-Final Inspection5/16/20135/17/20135/17/2013AFAIL
DetailsTroy Cobbley
Move the alarm bells to the front/street of the buildings and provide orfice in the inspectors test that matches the smallest orfice sprinkler used.
INSP-Sprinkler Rough-in4/25/20134/26/20134/26/2013APASS
DetailsTroy Cobbley
Another residence is ok to cover. See sticker on window.
INSP-Sprinkler Rough-in3/29/20133/29/20133/29/2013PDEFR
DetailsForrest France
lonnie Phone #: ###-#### *Incorrect permit number requested for inspection
INSP-Sprinkler Rough-in3/20/20133/20/20133/20/2013PPASS
DetailsTroy Cobbley
Tenting passed. "Ok to cover" posted on window.
INSP-Sprinkler Rough-in3/7/20133/7/20133/7/2013PPART
DetailsTroy Cobbley
Rough-in passed but piping can't be covered until the tenting is completed/inspected.
INSP-Sprinkler Rough-in2/4/20132/5/20132/5/2013APASS
DetailsTroy Cobbley
Sprinkler piping ok to cover in the far left unit. Tenting was repaired in two locations as I waited.
INSP-Sprinkler Rough-in1/31/20132/1/20132/1/2013ANR
DetailsForrest France
lonnie Phone #: ###-#### *Tenting/insulation incomplete
INSP-Sprinkler Rough-in12/31/201212/31/201212/31/2012PPART
DetailsTroy Cobbley
See the city approved plans for residences where the sprinkler rough-in is approved. I noted in two locations where pendant sprinkler heads are missing. Piping can not be covered until a tenting inspection has bee approved.
INSP-Sprinkler Rough-in12/19/201212/19/201212/19/2012PPASS
DetailsTroy Cobbley
See the city approved plans for the tenant space/residence where the piping rough-in passed. The walkin shower needs to be totally enclosed, as per discussion, or sprinkler protection required. Lonnie is going to move the pendant head over 2" in the master bath so that coverage is provided under the soffit. As per a later telephone dicussion with Lonnie, he is going to add a pendant in the entry way to provide coverage on the far side of a surface mounted light fixture. As-builts will be needed showing these changes and the deletion of one pendant in a storage area that is now a 1/2 bath. Sprinkler piping can not be covered until a tenting inspection has been completed.
Issue and Print Permit  12/18/2012 DONE
Plan assigned to (Tim)12/4/2012 12/13/2012 DONE
DetailsTim Frost
Plan assigned to (Tim)12/4/2012 12/13/2012 DONE
DetailsTim Frost
Sprinkler Plan Check12/13/2012 12/13/2012 PASS
DetailsTim Frost
Please, see attached comments.
There are NO annotations on the plans.
PLANS/APPL TAKEN TO FRONT DESK  12/13/2012 DONE
DetailsTim Frost
Telephone call  12/13/2012 DONE
DetailsChristina Prado
called Jon to advise permit is ready
Inspection Record Card- Fire12/13/2012 12/13/2012 DONE
DetailsChristina Prado
Permit Ready to Issue  12/13/2012 DONE
DetailsChristina Prado
Plan resubmittals received  12/11/2012 DONE
DetailsChristina Prado
recceived three sets of plans, applicationa and submittal documents; gave to Tim for further review
Sprinkler Plan Check12/6/2012 12/6/2012 FAIL
DetailsTim Frost
Please, see attached comments.
There are NO annotations on the plans.
1st review completed  12/6/2012 FAIL
DetailsTim Frost
Miscellaneous action  12/6/2012 DONE
DetailsTim Frost
Emailed review to contractor
Telephone call  12/6/2012 DONE
DetailsTisha Gallop
called Jon Edes and left vm to pick up denied plans
Application received  12/4/2012