Miscellaneous action | | | 4/8/2013 | | DONE |
Tim Frost
|
|
|
Sent to Records for scanning.
|
INSP-Final Inspection | 1/11/2013 | 1/14/2013 | 1/14/2013 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Sprinkler Rough-in | 1/11/2013 | 1/11/2013 | 1/11/2013 | P | PASS |
Troy Cobbley
|
|
|
Rough-in passed. Sprinkler piping is ok to cover.
|
Override - Parcel Holds | 1/11/2013 | 1/1/1900 | 1/11/2013 | | |
|
|
|
Fire final only
|
INSP-Sprinkler Rough-in | 1/9/2013 | 1/9/2013 | 1/9/2013 | P | FAIL |
Troy Cobbley
|
|
|
Pipe sizing for the new branchline does not match plans or the hydraulic calculations. Also the first pendant head on this new line was not installed as per plan and as a result coverage is lacking at the office wall. Additional access needs to be provided to see all of the piping and hangers that are concealed above the ceiling.
|
Override - Parcel Holds | 1/9/2013 | 1/1/1900 | 1/9/2013 | | |
|
|
|
fir cover only
|
Override - Parcel Holds | | | 1/8/2013 | | |
|
|
|
|
Issue and Print Permit | | | 1/8/2013 | | DONE |
Barbara Stitt
|
|
|
|
Plan assigned to (Tim) | 12/14/2012 | | 1/7/2013 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 1/7/2013 | | 1/7/2013 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/7/2013 | | DONE |
Tim Frost
|
|
|
|
Override - Parcel Holds | | | 1/7/2013 | | |
|
|
|
|
Permit Ready to Issue | | | 1/7/2013 | | |
|
|
|
|
Telephone call | | | 1/7/2013 | | |
|
|
|
1-7-13 called American Fire Protection- permit ready and fee given ///dld
|
Override - Parcel Holds | | | 1/7/2013 | | |
|
|
|
|
Inspection Record Card- Fire | 1/7/2013 | | 1/7/2013 | | DONE |
Darla L Downs
|
|
|
|
Plan resubmittals received | | | 1/4/2013 | | DONE |
Tisha Gallop
|
|
|
received three copies of application, submittal documents and plans; routed to Fire.
|
Sprinkler Plan Check | 12/19/2012 | | 12/19/2012 | | FAIL |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 12/19/2012 | | FAIL |
Tim Frost
|
|
|
|
Telephone call | | | 12/19/2012 | | DONE |
Barbara Stitt
|
|
|
Called and left a message that plans need picked up and re-submitted on 12-19-12 @ 3:15pm///BAS
|
Application received | | | 12/14/2012 | | |
|
|
|
|
Case Summary | | | 12/14/2012 | | DONE |
|
|
|
|