Permit Information
Permit NumberFIR12-00744
StatusFinaled
Name CRANE ALARM COMPANY
Site Address 1450 S EAGLE FLIGHT WAY Unit: 125
Project NameQuail Court Ste# 125
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to extend the existing fire alarm system and notification in to the new tenant space.
Associated building permit: BLD12-03154
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
(F) Reprint permit  7/8/2014 DONE
DetailsCandy A. Nichols
Miscellaneous action  4/16/2013 DONE
Plans taken to records for scanning
INSP-Final Inspection3/14/20133/15/20133/15/2013APASS
DetailsTroy Cobbley
permit finaled
CHANGE STATUS TO (ISS)  3/14/2013 DONE
DetailsBarbara Stitt
(F) Reprint permit  3/14/2013 DONE
DetailsBarbara Stitt
Alarm Plan Check3/12/2013 3/12/2013 FAIL
DetailsStephanie L. Cobbley
plan modification denied - previous redlines not addressed.
Telephone call  3/12/2013 DONE
Spoke to Tim at Crane Alarm to let him know I need to deny the plans because previous redlines were not incorporated. He said he would pick up the denied set later this afternoon.
Miscellaneous action  3/12/2013 DONE
Placed denied submittals in drawer at permit desk.
Plan resubmittals received  3/12/2013 DONE
DetailsChristina Prado
received two sets of plans, applications, checklists & required submittal docs; routed to steph for review
Alarm Plan Check3/12/2013 3/12/2013 PASS
DetailsStephanie L. Cobbley
Plan modification resubmittals approved
PLANS TAKEN FRONT DESK ALARM  3/12/2013 DONE
approved plans taken to permit technician for processing.
Inspection Record Card- Fire3/12/2013 3/12/2013 DONE
DetailsBarbara Stitt
Permit Ready to Issue  3/12/2013 DONE
DetailsBarbara Stitt
Plan assigned to (Stephanie)3/7/2013 3/12/2013 DONE
DetailsStephanie L. Cobbley
Plan modification
Plan resubmittals received  3/7/2013  
PLan Modification
INSP-Final Inspection1/16/20131/17/20131/17/2013PFAIL
DetailsTroy Cobbley
The audible notification devices are not synchronized as required per NFPA 72 18.4.2.5 . The tenant area new devices do not sync with the existing area corridor devices.
INSP-Final Inspection1/15/20131/16/20131/16/2013PCANC
DetailsTroy Cobbley
Cancel per tim Phone #: ###-####
INSP-Final Inspection1/8/20131/8/20131/8/2013PFAIL
DetailsTroy Cobbley
The new 15cd strobe in the corridor is overspaced. Also notification needs to be extended into the corridor in front of the restrooms since the door that is shown on the building plans has not been installed. No testing was actually performed. All other spacing within the tenant space appears ok. Tim and I discussed options.
Telephone call  1/8/2013 DONE
Inspector Cobbley called to discuss redlines I put on the floorplan. There were two areas/spaces that were not labeled for use, so I stated these areas would need to be field verified for use and notification requirements. The area the the north of device NO;3-2 was verified to be a small corridor leading from the tenant space to a restroom corridor. The door shown separating the restroom corridor from this space is not actually there. Because the building permit scope of work included this area due to door hardware requirements, it makes it part of the fire alarm scope of work as well. This space requires a notification device due to its use (which the contractor did install). However, because the 2nd door is not there, it is open to the restroom corridor and requires notification in that space as well under this permit. I let the inspector know that any other notification deficiencies outside the spaces mentioned above would need to be turned over to the fire department and would not affect this permit scope of work. This building does require full notification due to greater than 100 occupant load above the lowest level of exit discharge.
Issue and Print Permit  12/27/2012 DONE
DetailsBarbara Stitt
Plan assigned to (Stephanie)12/20/2012 12/24/2012 DONE
DetailsStephanie L. Cobbley
1st review completed  12/24/2012 PASS
Alarm Plan Check12/24/2012 12/24/2012 PASS
DetailsStephanie L. Cobbley
Plans approved with redlines and review comments.
PLANS TAKEN FRONT DESK ALARM  12/24/2012 DONE
Approved redlined plans taken to permit technician for processing.
Inspection Record Card- Fire12/24/2012 12/24/2012 DONE
DetailsDarla L Downs
Permit Ready to Issue  12/24/2012  
Permit Ready to Issue  12/24/2012  
Telephone call  12/24/2012  
12-24-12 called Crane Alarm Company left message permit ready and fee given ///dld
Application received  12/20/2012 DONE
DetailsBarbara Stitt