Miscellaneous action | | | 2/14/2013 | | DONE |
|
|
|
Plans taken to records for scanning
|
INSP-Final Inspection | 2/4/2013 | 2/4/2013 | 2/4/2013 | P | PASS |
Forrest France
|
|
|
Corrections verified. Fire alarm permit finaled.
|
INSP-Final Inspection | 1/16/2013 | 1/17/2013 | 1/17/2013 | P | PART |
Forrest France
|
|
|
Provide WP strobe at one location per plan, need to verify coverage at both conference rooms when construction is complete. Remainder of appliances tested okay.
|
Issue and Print Permit | | | 1/9/2013 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 1/2/2013 | | 1/8/2013 | | DONE |
Stephanie L. Cobbley
|
|
|
|
1st review completed | | | 1/8/2013 | | PASS |
|
|
|
|
Alarm Plan Check | 1/8/2013 | | 1/8/2013 | | PASS |
Stephanie L. Cobbley
|
|
|
Plans approved with redlines and review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 1/8/2013 | | DONE |
|
|
|
Approved redlined plans taken to permit technician for processing.
|
Inspection Record Card- Fire | 1/8/2013 | | 1/8/2013 | | DONE |
Christina Prado
|
|
|
|
Permit Ready to Issue | | | 1/8/2013 | | DONE |
Christina Prado
|
|
|
|
Telephone call | | | 1/8/2013 | | DONE |
Christina Prado
|
|
|
called David to advise permit is ready and gave fees due
|
Application received | | | 1/2/2013 | | |
|
|
|
|