INSP-Final Inspection | 2/20/2013 | 2/20/2013 | 2/20/2013 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
Fees Due Hold | 2/20/2013 | | 2/20/2013 | | DONE |
|
|
|
|
Issue permit | | | 2/20/2013 | | DONE |
|
|
|
Payment received via Govolutions
|
INSP-Final Inspection | 2/19/2013 | 2/20/2013 | 2/20/2013 | A | CANC |
Troy Cobbley
|
|
|
There is a fees hold on this project. Fees need payed prior to another inspection.
|
INSP-Final Inspection | 2/19/2013 | 2/19/2013 | 2/19/2013 | P | FAIL |
Forrest France
|
|
|
New strobe at the west side did not operate. Remainder of previous correction items completed.
|
INSP-Final Inspection | 2/15/2013 | 2/15/2013 | 2/15/2013 | P | FAIL |
Forrest France
|
|
|
Correction items include damper operations, notification appliances per 18.3.3.2, agent release signage, openings at the room enclosure.
|
INSP-Final Inspection | 2/11/2013 | 2/12/2013 | 2/12/2013 | A | NR |
Forrest France
|
|
|
Final pending panel supervision
|
Plan assigned to (Tim) | 1/15/2013 | | 1/23/2013 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 1/23/2013 | | 1/23/2013 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/23/2013 | | DONE |
Tim Frost
|
|
|
|
Permit Ready to Issue | | | 1/23/2013 | | DONE |
Christina Prado
|
|
|
|
Issue and Print Permit | | | 1/23/2013 | | DONE |
Christina Prado
|
|
|
|
Inspection Record Card- Fire | 1/23/2013 | | 1/23/2013 | | DONE |
Christina Prado
|
|
|
|
Sprinkler Plan Check | 1/15/2013 | | 1/15/2013 | | FAIL |
Tim Frost
|
|
|
Please see attached comments
|
Miscellaneous action | | | 1/15/2013 | | DONE |
Tim Frost
|
|
|
Emailed review to contractor
|
Application received | | | 1/11/2013 | | DONE |
|
|
|
Application submitted via PDS Online on Jan 11 2013 10:23AM
|