Permit Information
Permit NumberFIR13-00042
StatusFinaled
Name TAYLOR BROTHERS FIRE & SAFETY INC
Site Address 1157 N MILWAUKEE
Project NameCost Plus
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to replace the existing damaged panel with new and re-connect existing devices. This permit scope of work includes monitoring the existing sprinkler system, adding a remote annunciator panel, adding a smoke detector above the panel, and providing a pull station. The existing return-side duct detectors are being replaced with new and are powered from the panel. The existing supply-side duct detectors are being removed. There is no associated building permit.
NOTE: approval was given to replace the panel prior to receiving approved plans due to the system not reporting because of damage.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  4/16/2013 DONE
Plans taken to records for scanning
INSP-Final Inspection2/14/20132/15/20132/15/2013APASS
DetailsTroy Cobbley
permit finaled
Issue and Print Permit  2/14/2013 DONE
DetailsBarbara Stitt
Plan assigned to (Stephanie)1/29/2013 2/7/2013 DONE
DetailsStephanie L. Cobbley
Miscellaneous action  2/7/2013 DONE
Received requested documentation
1st review completed  2/7/2013 PASS
Alarm Plan Check2/7/2013 2/7/2013 PASS
DetailsStephanie L. Cobbley
Plans approved with review comments
PLANS TAKEN FRONT DESK ALARM  2/7/2013 DONE
approved plans taken to permit technician for processing.
Permit Ready to Issue  2/7/2013 DONE
DetailsTisha Gallop
Inspection Record Card- Fire2/7/2013 2/7/2013 DONE
DetailsTisha Gallop
Telephone call  2/7/2013 DONE
DetailsTisha Gallop
called Mary and left mssg permit is ready and fee due.
Telephone call  2/6/2013 DONE
Spoke to Mary at Taylor Brothers. I explained that the plans that were submitted do not reflect what will actually be installed per a conversation with Micheal from Taylor Brothers. I told her that I could approve these the way they were submitted, but then a plan modification (additional fees involved) would be required prior to calling for a final inspection. She said she thought plans were brought to me yesterday to replace the ones I have. I told her I'd wait until this afternoon to see if the plans are brought in before either denying the plans or approving w/ the plan modification option.
Miscellaneous action  2/5/2013 DONE
A question about the type of tamper switch and supervisory signal means came up. The contractor emailed me data sheets and I let him know that as long as the connection to the fire alarm panel and the supervisory signals meet the following, then we would accept it: 2010 NFPA 72 10.11.3 Self-Restoring Supervisory Signal Indication. Visible and audible indication of self-restoring supervisory signals and visible indication of their restoration to normal shall be automatically indicated within 90 seconds at the following locations:
(1) Fire alarm control unit for local fire alarm systems
(2) Building fire command center for in-building fire emergency
voice/alarm communications systems
(3) Supervising station location for systems installed in compliance with Chapter 26
Miscellaneous action  1/29/2013 DONE
Approved the panel to be replaced prior to approved plans. The original panel was shorted out and non-functioning.
Application received  1/29/2013