Miscellaneous action | | | 4/16/2013 | | DONE |
|
|
|
Plans taken to records for scanning
|
INSP-Final Inspection | 2/14/2013 | 2/15/2013 | 2/15/2013 | A | PASS |
Troy Cobbley
|
|
|
permit finaled
|
Issue and Print Permit | | | 2/14/2013 | | DONE |
Barbara Stitt
|
|
|
|
Plan assigned to (Stephanie) | 1/29/2013 | | 2/7/2013 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Miscellaneous action | | | 2/7/2013 | | DONE |
|
|
|
Received requested documentation
|
1st review completed | | | 2/7/2013 | | PASS |
|
|
|
|
Alarm Plan Check | 2/7/2013 | | 2/7/2013 | | PASS |
Stephanie L. Cobbley
|
|
|
Plans approved with review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 2/7/2013 | | DONE |
|
|
|
approved plans taken to permit technician for processing.
|
Permit Ready to Issue | | | 2/7/2013 | | DONE |
Tisha Gallop
|
|
|
|
Inspection Record Card- Fire | 2/7/2013 | | 2/7/2013 | | DONE |
Tisha Gallop
|
|
|
|
Telephone call | | | 2/7/2013 | | DONE |
Tisha Gallop
|
|
|
called Mary and left mssg permit is ready and fee due.
|
Telephone call | | | 2/6/2013 | | DONE |
|
|
|
Spoke to Mary at Taylor Brothers. I explained that the plans that were submitted do not reflect what will actually be installed per a conversation with Micheal from Taylor Brothers. I told her that I could approve these the way they were submitted, but then a plan modification (additional fees involved) would be required prior to calling for a final inspection. She said she thought plans were brought to me yesterday to replace the ones I have. I told her I'd wait until this afternoon to see if the plans are brought in before either denying the plans or approving w/ the plan modification option.
|
Miscellaneous action | | | 2/5/2013 | | DONE |
|
|
|
A question about the type of tamper switch and supervisory signal means came up. The contractor emailed me data sheets and I let him know that as long as the connection to the fire alarm panel and the supervisory signals meet the following, then we would accept it: 2010 NFPA 72 10.11.3 Self-Restoring Supervisory Signal Indication. Visible and audible indication of self-restoring supervisory signals and visible indication of their restoration to normal shall be automatically indicated within 90 seconds at the following locations:
(1) Fire alarm control unit for local fire alarm systems
(2) Building fire command center for in-building fire emergency
voice/alarm communications systems
(3) Supervising station location for systems installed in compliance with Chapter 26
|
Miscellaneous action | | | 1/29/2013 | | DONE |
|
|
|
Approved the panel to be replaced prior to approved plans. The original panel was shorted out and non-functioning.
|
Application received | | | 1/29/2013 | | |
|
|
|
|