Information based on query as of Saturday, August 17, 2024.
Permit Information
Permit NumberFIR13-00043
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 12352 W FAIRVIEW AVE
Project NamePeterson Chevrolet (Chemical S
Customer Number 
ePlanReviewYes
Description
The fire sprinkler scope of work consists of providing protection for the storage area, tool room, oil room(s) and compressor room. The storage area has a mezzanine. Each level of the storage area is protected by a grid. There are flammable and combustible liquids in plastic containers. This commodity is not prescribed in NFPA 13 and NFPA 30. Therefore, FM data sheets were consulted. Through a long chain of references the final design criteria was found in FM 7-32 table 3. (.30/4000 +500 hose, K=8.0, SR, High Temperature sprinklers)

The other fire protection systems for this building were installed under permit FIR12-00574
The underground was installed under permit FIR12-00330
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/11/20134/12/20134/12/2013APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection4/11/20134/11/20134/11/2013PFAIL
DetailsTroy Cobbley
As-builts were not on site for review.
INSP-Final Inspection4/10/20134/11/20134/11/2013AFAIL
DetailsTroy Cobbley
Valve for the forward flush broke and the plan modifications were not on site for review.
INSP-Sprinkler Rough-in4/3/20134/4/20134/4/2013PPART
DetailsTroy Cobbley
Rough-in is ok but need verification that additional fittings in the upper and lower storage room sprinkler system do not adversly effect the hydraulic calculations. Need model number of the air compressor verified for the 4.5 cfm requirement. Need to verify that the backflow preventor is ok (wrong model number). Need approved notes for review. Need storage signage per note #5. As-builts, if time does not require resubmittals, showing the additional piping and heads under both stairways. Also solid shelving has been installed, some of which is 8' x 24'. I contacted Cam and Tim Frost and I'm waiting for an official responce if this shelving is ok.
INSP-Sprinkler Rough-in3/1/20133/4/20133/4/2013ACANC
DetailsTroy Cobbley
I stopped at the job site but the plans are locked in the job box. Per Mark Jensen the inspection will be rescheduled.
INSP-Sprinkler Rough-in2/28/20133/1/20133/1/2013ACANC
DetailsTroy Cobbley
Overbooked. Rescheduled for monday. I spoke to Mike with Shilo about this.
INSP-Sprinkler Rough-in2/28/20132/28/20132/28/2013PPART
DetailsTroy Cobbley
See the city approved plans for locations in the main shop/service area and detail/carwash areas where corrections are required. The plans need to be re-submitted showing the additional branchline and heads which will effect the remote areas. Branch line restraints and retaining straps are missing in several locations. Pipe clearance at the CMU penatrations are not big enough....ect.
Sprinkler Plan Check2/6/2013 2/6/2013 PASS
DetailsTim Frost
Please, see attached comments.
PLANS/APPL TAKEN TO FRONT DESK  2/6/2013 DONE
DetailsTim Frost
Issue and Print Permit  2/6/2013 DONE
DetailsTisha Gallop
Inspection Record Card- Fire2/6/2013 2/6/2013 DONE
DetailsTisha Gallop
Plan assigned to (Tim)1/31/2013 1/31/2013 DONE
DetailsTim Frost
Sprinkler Plan Check1/31/2013 1/31/2013 FAIL
DetailsTim Frost
Please, see attached comments.
There are annotations on the plans.
1st review completed  1/31/2013 FAIL
DetailsTim Frost
Application received  1/30/2013 DONE
Application submitted via PDS Online on Jan 30 2013 8:06AM