Miscellaneous action | | | 9/25/2013 | | DONE |
|
|
|
Scanned application into Tidemark and Onbase
|
INSP-Final Inspection | 6/6/2013 | 6/7/2013 | 6/7/2013 | A | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Final Inspection | 5/31/2013 | 6/6/2013 | 6/6/2013 | A | FAIL |
Troy Cobbley
|
|
|
Provide adjustment for the PIV and test
|
Telephone call | | | 5/16/2013 | | DONE |
|
|
|
Brent P. with LCA Architects left a message regarding the knox box requirement on the review comments. He asked if they could eliminate the knox box due to the type of secure facility they have. I left him a message letting him know that was acceptable.
|
INSP-Final Inspection | 4/26/2013 | 4/26/2013 | 4/26/2013 | P | FAIL |
Troy Cobbley
|
|
|
Todays inspection request was just for a walk through to verify spacing/layout of the devices that have been installed. See the city approved plans for acouple of locations where corrections are needed. I deferred approval of the smoke detectors located in the sky lights to the fire dept. since they exceed 12" from the deck. Clay Freinwald Phone #: ###-####
|
Issue and Print Permit | | | 2/14/2013 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 2/4/2013 | | 2/12/2013 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Telephone call | | | 2/12/2013 | | DONE |
|
|
|
Spoke to Geoff at Eidam and was given the clarification needed to proceed with the review.
|
1st review completed | | | 2/12/2013 | | PASS |
|
|
|
|
Alarm Plan Check | 2/12/2013 | | 2/12/2013 | | PASS |
Stephanie L. Cobbley
|
|
|
Plans approved with review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 2/12/2013 | | DONE |
|
|
|
Approved plans taken to permit technician for processing.
|
Telephone call | | | 2/12/2013 | | DONE |
Christina Prado
|
|
|
called Daric to give fees due and let know permit is ready
|
Permit Ready to Issue | | | 2/12/2013 | | DONE |
Christina Prado
|
|
|
|
Inspection Record Card- Fire | 2/12/2013 | | 2/12/2013 | | DONE |
Christina Prado
|
|
|
|
Miscellaneous action | | | 2/11/2013 | | DONE |
|
|
|
Emailed Rob Ahten with Protex requesting additional design information for the VESDA system in accordance with NFPA 72 requirements. I let him know I need the information by this Friday.
|
Telephone call | | | 2/11/2013 | | DONE |
|
|
|
Left a message for Geoff Johnson w/ Eidam & Assoc. regarding areas that appear to be exposed to the exterior, but I need verification.
|
Telephone call | | | 2/11/2013 | | DONE |
|
|
|
Rob w/ Protex called and answered my questions regarding the VESDA system. No additional details or sheets necessary for this issue.
|
Application received | | | 2/4/2013 | | |
|
|
|
|