Miscellaneous action | | | 9/23/2013 | | DONE |
Lee G Meredith
|
|
|
Scanned application into Tidemark, copied Hattie
|
INSP-Final Inspection | 3/5/2013 | 3/7/2013 | 3/7/2013 | A | PASS |
Forrest France
|
|
|
Fire alarm work passed functional testing. Permit final approved.
|
Issue and Print Permit | | | 2/26/2013 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 2/19/2013 | | 2/25/2013 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Telephone call | | | 2/25/2013 | | DONE |
|
|
|
Spoke to Dave at Nelson Fire Systems asking him to send an email verifying the speaker calcs/watts availablility.
|
Miscellaneous action | | | 2/25/2013 | | DONE |
|
|
|
Received an email from Dave at Nelson Fire letting me know that the existing speaker circuit has 21 devices each tapped at .5 watt. They are adding two speakers which will be tapped at .5 watt each. The total available capacity per circuit is 50 watts. The total wattage for the circuit will be 11.5 watts, leaving 38.5 watts spare.
|
Alarm Plan Check | 2/25/2013 | | 2/25/2013 | | PASS |
Stephanie L. Cobbley
|
|
|
Quick permit approved - no written review comments - see redlines on plans
|
PLANS TAKEN FRONT DESK ALARM | | | 2/25/2013 | | DONE |
|
|
|
Approved quick permit plans taken to permit technician for processing.
|
Inspection Record Card- Fire | 2/25/2013 | | 2/25/2013 | | DONE |
Christina Prado
|
|
|
|
Permit Ready to Issue | | | 2/25/2013 | | DONE |
Christina Prado
|
|
|
|
Telephone call | | | 2/25/2013 | | DONE |
Christina Prado
|
|
|
called Phil to advise permit is ready
|
Telephone call | | | 2/22/2013 | | DONE |
|
|
|
Spoke to Dave with Nelson Fire regarding the information I need for the resubmittal. He said he would make the changes and email me the requested information.
|
Miscellaneous action | | | 2/22/2013 | | DONE |
|
|
|
Received requested information
|
Telephone call | | | 2/20/2013 | | DONE |
|
|
|
Spoke to Phill Bassick at Tri-state letting him know I need to reject the quick permit plans. The plans are not to scale, they are not legible, there are no room names/uses provided, no speaker/wattage calculations were provided, keyed notes are referenced on the plans but there are no notes to correspond with them, etc..He said he undertands and appreciated the notification. He said he is going to have the designer get in touch with me.
|
1st review completed | | | 2/20/2013 | | FAIL |
|
|
|
|
Alarm Plan Check | 2/20/2013 | | 2/20/2013 | | FAIL |
Stephanie L. Cobbley
|
|
|
quick permit plans denied - see phone call notes
|
Application received | | | 2/19/2013 | | |
|
|
|
|