Permit Information
Permit NumberFIR13-00087
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 4120 N EAGLE RD
Project NameBioLife Plasma Services
Customer Number 
ePlanReviewYes
Description
This fire alarm permit is to provide a voluntary manual system with partial smoke detection in a new building. This permit scope of work includes notification, pull stations at every exit (requested by the owner), smoke detectors in restrooms, closets, and other rooms not often frequented or checked on by employees, HVAC shutdown/monitoring, and sprinkler system monitoring.
Associated building permit: BLD12-02045
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/2/20137/2/20137/2/2013PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection7/1/20137/1/20137/1/2013PFAIL
DetailsTroy Cobbley
Need as-builts showing the manual pull station at the entrance being relocated and the addition of a monitor module for the PIV. Also one hvac unit would not shut down under heat mode and the other hvac unit would not go into heat mode so that we could test the duct smoke detector. All other devices tested ok.
INSP-Alarm Testing6/28/20136/28/20136/28/2013PFAIL
DetailsTroy Cobbley
No approved plans on site. No inspection performed. Also the sprinkler contractor was performing a hydro test.
Telephone call  2/28/2013 DONE
Spoke to T.J. at Nelson Electric Co. (designer) regarding questions I had about the design:
1)This building is not required by code to have anything other than Sprinkler and HVAC monitoring. Is this a voluntary system? ANSWER: Yes
2)The scope of work states a complete automatic detection system, however there are not smoke detectors throughout. Please verify the intent. ANSWER: This is intended as a partial coverage system to provide smoke detection in restrooms, closets, and other spaces that are not frequently occupied or frequently checked on by employees (due to potential unpredictable clientele)
3)This is a fully sprinklered building, therefore only one pull station is required. Are the additional pull stations wanted? ANSWER: yes, per owner’s request
4)Please state the uses of rooms Ante 131 and Biohazard 120 for verification of notification requirements. ANSWER: Both rooms are storage rooms
5)The City of Boise does not require exterior visual notification (the sprinkler flow bell is all that is required for exterior sprinkler flow notification), is this device still desired? ANSWER: Yes, per owner request.
1st review completed  2/28/2013 PASS
Alarm Plan Check2/28/2013 2/28/2013 PASS
DetailsStephanie L. Cobbley
Plans approved with review comments and some plan notes
PLANS TAKEN FRONT DESK ALARM  2/28/2013 DONE
plans approved and updated in project dox
Permit Ready to Issue  2/28/2013 DONE
Issue and Print Permit  2/28/2013 DONE
(F) Reprint permit  2/28/2013 DONE
(F) Reprint permit  2/28/2013 DONE
DetailsChristina Prado
Inspection Record Card- Fire2/28/2013 2/28/2013 DONE
DetailsChristina Prado
Application received  2/26/2013 DONE
Application submitted via PDS Online on Feb 26 2013 2:28PM
Miscellaneous action  2/26/2013 DONE
pre-screen accepted
Plan assigned to (Stephanie)2/26/2013 2/26/2013 DONE
DetailsStephanie L. Cobbley
Miscellaneous action  2/26/2013 DONE
SimplexGrinnell emailed and asked that I 'swap' the review order with FIR13-00081.