INSP-Final Inspection | 4/4/2013 | 4/5/2013 | 4/5/2013 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
Telephone call | | | 3/11/2013 | | DONE |
|
|
|
Called Bret to go over the plans. The device still appears to be overspaced, however he did not have an accurate scaled bar graph so I could not calibrate project dox to view it properly. He assured me that the device is not overspaced. I agreed to make this a field verify.
|
Alarm Plan Check | 3/11/2013 | | 3/11/2013 | | PASS |
Stephanie L. Cobbley
|
|
|
quick permit re-submittals approved - no written review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 3/11/2013 | | DONE |
|
|
|
updated in project dox
|
Permit Ready to Issue | | | 3/11/2013 | | DONE |
Tisha Gallop
|
|
|
|
Issue and Print Permit | | | 3/11/2013 | | DONE |
Tisha Gallop
|
|
|
|
Inspection Record Card- Fire | 3/11/2013 | | 3/11/2013 | | DONE |
Tisha Gallop
|
|
|
|
Plan resubmittals received | | | 3/5/2013 | | DONE |
|
|
|
|
1st review completed | | | 3/1/2013 | | FAIL |
|
|
|
|
Alarm Plan Check | 3/1/2013 | | 3/1/2013 | | FAIL |
Stephanie L. Cobbley
|
|
|
candela is not sized to provide adequate visual coverage for space. Increase candela rating and/or provide additional devices. Revise plans, one-line diagram, and provide battery calcs/voltage drops.
|
Miscellaneous action | | | 3/1/2013 | | DONE |
|
|
|
updated in project dox
|
Telephone call | | | 3/1/2013 | | DONE |
|
|
|
Called Bret w/Mountain Alarm to let him know I need to deny the plans.
|
Application received | | | 2/28/2013 | | DONE |
|
|
|
Application submitted via PDS Online on Feb 28 2013 9:03AM
|
Plan assigned to (Stephanie) | 2/28/2013 | | 2/28/2013 | | DONE |
Stephanie L. Cobbley
|
|
|
|