INSP-Final Inspection | 5/8/2013 | 5/10/2013 | 5/10/2013 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 4/23/2013 | 4/26/2013 | 4/26/2013 | A | FAIL |
Troy Cobbley
|
|
|
Wire the duct smoke detectors to shut down the hvac units immediatley per IMC, resend signals for the tamper switches to verify "supervisory" signals are sent to central station and provide map and close out documents.
|
Permit Ready to Issue | | | 4/1/2013 | | DONE |
|
|
|
|
Issue and Print Permit | | | 4/1/2013 | | DONE |
Tisha Gallop
|
|
|
|
Inspection Record Card- Fire | 4/1/2013 | | 4/1/2013 | | DONE |
Tisha Gallop
|
|
|
|
Alarm Plan Check | 3/26/2013 | | 3/26/2013 | | PASS |
Stephanie L. Cobbley
|
|
|
resubmittals approved with review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 3/26/2013 | | DONE |
|
|
|
updated in project dox
|
Plan resubmittals received | | | 3/25/2013 | | DONE |
|
|
|
|
Telephone call | | | 3/12/2013 | | DONE |
|
|
|
Spoke to Dave w/ Tyco. He explained that he does not have an accurate account of type/quantity of sprinkler valves to be monitored. I told him I could approve as submitted, however if additional devices need to be added it would need to be done under a plan modification and additional fees would be applied. The other option I gave was to deny the plans and he could re-submit when he does have an accurate count, thus only one set of fees. He opted to have me deny the plans.
|
1st review completed | | | 3/12/2013 | | FAIL |
|
|
|
|
Alarm Plan Check | 3/12/2013 | | 3/12/2013 | | FAIL |
Stephanie L. Cobbley
|
|
|
plans denied - accurate counts of devices are unknown.
|
Miscellaneous action | | | 3/12/2013 | | DONE |
|
|
|
updated in project dox
|
Telephone call | | | 3/11/2013 | | DONE |
|
|
|
Left a message for Dave at Tyco. A low-air switch is indicated but none of the other valves typically associated with it is shown. I asked for him to call me back with clarification.
|
Plan assigned to (Stephanie) | 3/5/2013 | | 3/5/2013 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Application received | | | 3/1/2013 | | DONE |
|
|
|
Application submitted via PDS Online on Mar 1 2013 2:27PM
|