Permit Information
Permit NumberFIR13-00110
StatusFinaled
Name FIRE SENTRY SYSTEMS
Site Address 475 W PARKCENTER BLVD
Project NameHoliday Inn Remodel
Customer Number 
ePlanReviewYes
Description
This fire alarm permit is to install visual notification in 8 new ADA rooms, revise visual notification in 8 hearing impaired rooms, and install pull stations at all exits from every level.
Associated building permit: BLD12-03273
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Case Summary  1/30/2014 DONE
INSP-Final Inspection7/25/20137/26/20137/29/2013PPASS
DetailsForrest France
Previously noted correction items verified for completion. Fire alarm permit finaled.
INSP-Final Inspection7/18/20137/23/20137/29/2013PFAIL
DetailsForrest France
Final pending additional coverage at adjoining guestrooms 312/314, room smokes to report as a supervisory condition, provide as-builts reflecting actual ADA room locations and correct CO addresses, post points map at the panel.
Plan resubmittals received  7/24/2013  
Received 2 copies of sheets FA1-, FA-2, FA-3, FA-4, FA-5
Case Summary  7/24/2013 DONE
INSP-Final Inspection7/15/20137/16/20137/16/2013AFAIL
DetailsForrest France
Need to provide WP notification devices at the guest room bathrooms per review notes, HT supervision and CO devices are not yet installed, field install does not correlate to the approved plan with regard to which rooms are ADA/hearing impared and provided with visual coverage, wall mount notification appliances should not be installed in a ceiling mount position. No testing performed due to modifications and adjustments necessary.
Telephone call  7/16/2013 DONE
DetailsLee G Meredith
Installing contractor, Earl of Fire Sentry, called to discuss today's acceptance test issues. He stated that the owner changed the quantity of accessible rooms so the actual quantity of accessible room verses that shown on the apporve drawings does not match. Earl wanted to know if a plan modification would be required. We discussed the fact that several other items had not been completed in time for the inspection and that a subsequent inspection request would be made in the future. I informed him that if all other issues were completely resolved and accepted at the next test and that these were the only issues with the plans that they could be noted corrections on the as built drawings but if there were any other items, then a plan mod would be required.
Plan assigned to (Lee)6/14/2013 6/17/2013 DONE
DetailsLee G Meredith
Plan Mod eplan review
Miscellaneous action  6/17/2013 DONE
DetailsLee G Meredith
Revisions completed and accepted.
Alarm Plan Check6/17/2013 6/17/2013 DONE
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  6/17/2013 DONE
DetailsLee G Meredith
CHANGE STATUS TO (ISS)  6/17/2013 DONE
DetailsTisha Gallop
plan mod approved and paid.
Miscellaneous action  6/14/2013 DONE
DetailsLee G Meredith
6/14/13

Here is a list of the things that changed which precipitated this plan mod submittal:

ADA room 206 was changed at the owners request to room 310.

ADA room 208 was changed at the owners request to room 312.

ADA room 209 was changed at the owners request to room 410.

ADA room 509 was changed at the owners request to room 412.

ADA room 508 was changed at the owners request to room 510.

ADA room 521 was changed at the owners request to room 512

The owner also added 5 CO detectors. There are two fireplaces in the 1st floor great room. One CO detector was placed in the middle of the great room, and one detector each in 4 2nd floor rooms directly above the two fireplaces.
The 5 CO detectors (installed by others) are now going to be monitored by the FACP via mini monitor modules. This was not required, but an owner requested change.

Lastly, there is existing heat tape at the top of the north stairwell (6th floor). We will monitor the heat tape with a mini monitor module.
Miscellaneous action  6/14/2013 PASS
DetailsLee G Meredith
Plan modification resubmitted. Minor issues on some drawings. Client will revise and resubmit.
Issue and Print Permit  5/23/2013  
Permit Ready to Issue  5/23/2013  
Inspection Record Card- Fire5/23/2013 5/23/2013 DONE
DetailsDarla L Downs
CHANGE STATUS TO (ISS)  5/23/2013  
Alarm Plan Check3/26/2013 3/26/2013 PASS
DetailsStephanie L. Cobbley
Plans approved with mark ups
PLANS TAKEN FRONT DESK ALARM  3/26/2013 DONE
updated in project dox
Plan resubmittals received  3/21/2013 DONE
1st review completed  3/18/2013 FAIL
Alarm Plan Check3/18/2013 3/18/2013 FAIL
DetailsStephanie L. Cobbley
plans denied - see change marks and review comments
Miscellaneous action  3/18/2013 DONE
updated status in project dox
Application received  3/8/2013 DONE
Application submitted via PDS Online on Mar 8 2013 2:24PM
Plan assigned to (Stephanie)3/8/2013 3/8/2013 DONE
DetailsStephanie L. Cobbley