Case Summary | | | 2/4/2014 | | |
|
|
|
|
INSP-Final Inspection | 9/30/2013 | 10/1/2013 | 10/1/2013 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 9/19/2013 | 9/23/2013 | 9/23/2013 | A | FAIL |
Troy Cobbley
|
|
|
Need the two duct smoke detectors to shut down the hvac units immediately to final this permit.
|
INSP-Final Inspection | 8/28/2013 | 9/4/2013 | 9/4/2013 | A | FAIL |
Troy Cobbley
|
|
|
New duct smoke detectors are listed to be mounted outside as per Joe with System Sensor. But duct smoke detectors were not wired up for power. Inspection stopped and will need to be resceduled.
|
INSP-Final Inspection | 8/9/2013 | 8/12/2013 | 8/12/2013 | A | FAIL |
Troy Cobbley
|
|
|
Provide knox box, provide map at facp, provide signage on FACP door, provide dedicated/locked out circuit for the FACP, provide listed enclosures for the duct smoke detectors and then test them, provide verification the kitchen hvac unit does not require a detector, provide correct zone descriptions at central station and retest everything
|
INSP-Final Inspection | 7/11/2013 | 7/12/2013 | 7/12/2013 | P | FAIL |
Troy Cobbley
|
|
|
Provide proof of payment for Bench Sewer Dist. (lee sperl ###-####), provide FIR permit for the hood suppression system, provide final inspection for the fire sprinkler permit. Test all fire alarm devices and adjust candella as discussed in the open area.
|
Override - Parcel Holds | 7/11/2013 | 1/1/1900 | 7/11/2013 | | |
|
|
|
fire alarm final
|
CHANGE STATUS TO (ISS) | | | 7/10/2013 | | DONE |
|
|
|
|
(F) Reprint permit | | | 7/10/2013 | | DONE |
|
|
|
|
Plan resubmittals received | | | 7/8/2013 | | DONE |
Christina Prado
|
|
|
Plan Modification - Received two sets of reviced plans, calcs and checklists; Routed to Lee for review
|
Plan assigned to (Lee) | 7/8/2013 | | 7/8/2013 | | DONE |
Lee G Meredith
|
|
|
|
Alarm Plan Check | 7/8/2013 | | 7/8/2013 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 7/8/2013 | | PASS |
Lee G Meredith
|
|
|
|
Override - Parcel Holds | | | 7/8/2013 | | |
|
|
|
|
Inspection Record Card- Fire | 7/8/2013 | | 7/8/2013 | | DONE |
Tisha Gallop
|
|
|
|
Override - Parcel Holds | | | 7/8/2013 | | |
|
|
|
|
Permit Ready to Issue | | | 7/8/2013 | | DONE |
|
|
|
|
Telephone call | | | 7/8/2013 | | DONE |
Tisha Gallop
|
|
|
called Tim Ezelle and left mssg plan mod is ready and fee
|
Plan assigned to (Lee) | 6/26/2013 | | 6/27/2013 | | DONE |
Lee G Meredith
|
|
|
|
Alarm Plan Check | 6/27/2013 | | 6/27/2013 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 6/27/2013 | | FAIL |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 6/27/2013 | | DONE |
Lee G Meredith
|
|
|
Failed plans taken to front desk for technician processing
|
Miscellaneous action | | | 6/27/2013 | | DONE |
Lee G Meredith
|
|
|
Emailed client plan review comments
|
Telephone call | | | 6/27/2013 | | DONE |
Tisha Gallop
|
|
|
called Crane Alarm and told Sherry plan failed and up at front desk for pick up
|
Plan resubmittals received | | | 6/26/2013 | | DONE |
Christina Prado
|
|
|
**PLAN MODIFICATION** Received two sets of revised plans, applications, specs and checklist
|
Issue and Print Permit | | | 3/25/2013 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 3/11/2013 | | 3/19/2013 | | DONE |
Stephanie L. Cobbley
|
|
|
|
1st review completed | | | 3/19/2013 | | PASS |
|
|
|
|
Alarm Plan Check | 3/19/2013 | | 3/19/2013 | | PASS |
Stephanie L. Cobbley
|
|
|
Plans approved with redlines and review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 3/19/2013 | | DONE |
|
|
|
approved plans taken to permit technician for processing.
|
Inspection Record Card- Fire | 3/19/2013 | | 3/19/2013 | | DONE |
Barbara Stitt
|
|
|
|
Permit Ready to Issue | | | 3/19/2013 | | DONE |
Barbara Stitt
|
|
|
|
Telephone call | | | 3/19/2013 | | DONE |
Barbara Stitt
|
|
|
Left message for Tim that permit is ready & fees due on 3-19-13 @ 10:25am///BAS
|
Application received | | | 3/11/2013 | | |
|
|
|
|