INSP-Final Inspection | 6/4/2013 | 6/4/2013 | 6/4/2013 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Conference | 5/31/2013 | 5/31/2013 | 5/31/2013 | P | DONE |
Troy Cobbley
|
|
|
I let Jason know that the manual pull stations for the emergency alert system do not meet code since they are red in color. The code section is: NFPA 72 17.14.1.2 Manual pull stations for initiating other than fire alarm shall be permitted if the devices are differentiated from the manual fire alarm boxes by a color other than red and labeling.
|
INSP-Alarm Testing | 5/28/2013 | 5/30/2013 | 5/30/2013 | A | FAIL |
Troy Cobbley
|
|
|
All items tested ok except the sprinkler interconnection have not been tested.
|
Permit Ready to Issue | | | 4/12/2013 | | DONE |
Christina Prado
|
|
|
|
Issue and Print Permit | | | 4/12/2013 | | DONE |
Christina Prado
|
|
|
|
Inspection Record Card- Fire | 4/12/2013 | | 4/12/2013 | | DONE |
Christina Prado
|
|
|
|
1st review completed | | | 4/9/2013 | | PASS |
|
|
|
|
Alarm Plan Check | 4/9/2013 | | 4/9/2013 | | PASS |
Stephanie L. Cobbley
|
|
|
Plans approved with markups and review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 4/9/2013 | | DONE |
|
|
|
updated in project dox
|
Plan assigned to (Stephanie) | 4/1/2013 | | 4/1/2013 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Application received | | | 3/21/2013 | | DONE |
|
|
|
Application submitted via PDS Online on Mar 21 2013 11:21AM
|