Permit Information
Permit NumberFIR13-00133
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 800 W MAIN ST
Project Name8th and Main Street Tower
Customer Number 
ePlanReviewYes
Description
Connect to existing 6" combination automatic standpipe and extend new wet systems into the 16th, 17th and penthouse levels to protect the levels in accordance with NFPA 13 light and ordinary hazards. This will complete the core and shell fire protection for this building.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/17/201312/17/201312/18/2013PPASS
DetailsForrest France
INSP-Final Inspection12/12/201312/13/201312/13/2013APART
DetailsForrest France
C/N items on 16th floor and the penthouse level.
INSP-Final Inspection11/27/201312/2/201312/3/2013APART
DetailsForrest France
Noted a large non-sprinklered area above the 17th floor SE corner, remove foil at upright heads in the penthouse, provide access to the electrical room penthouse level for inspection, need signage at the control valve for the roof top hose connection, upright at the 16th floor service elevator lobby is blocked. 17th floor TI work underway.
INSP-Final Inspection11/19/201311/22/201311/26/2013ANR
DetailsForrest France
Mike B is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in/Hydro7/30/20137/31/20137/31/2013APART
DetailsForrest France
OH hydrostatic test completed for the 16th and 17th floors.
INSP-Sprinkler Rough-in7/30/20137/31/20137/31/2013APART
DetailsForrest France
Preliminary rough-in inspection of the penthouse system only. Some areas incompleted or not yet constructed including the electrical room, top of stairway, south end duct, sheetrock at walls. Discussed possible obstructions.
INSP-Sprinkler Rough-in6/4/20136/6/20136/6/2013APART
DetailsForrest France
Shell system rough-in completed for the 16th and 17th floors. Noted five areas on the 17th floor and two areas on the 16th floor in need of revision- field changes to piping layout in the remote calc area on the 16th floor, floorplan change on the 17th floor SW corner, missing and obstructed heads at some locations, overspaced coverage at the mens restroom 17th floor. Coverage below ductwork incomplete at this time.
Sprinkler Plan Check4/1/2013 4/1/2013 PASS
DetailsTim Frost
Please, see attached comments.
PLANS/APPL TAKEN TO FRONT DESK  4/1/2013 DONE
DetailsTim Frost
Permit Ready to Issue  4/1/2013 DONE
Issue and Print Permit  4/1/2013 DONE
Inspection Record Card- Fire4/1/2013 4/1/2013 DONE
DetailsAlexandra L. DeYoung
Sprinkler Plan Check3/26/2013 3/26/2013 FAIL
DetailsTim Frost
Please, see attached comments.
1st review completed  3/26/2013 FAIL
DetailsTim Frost
Miscellaneous action  3/26/2013 DONE
DetailsTim Frost
Emailed review to contractor
Plan assigned to (Tim)3/25/2013 3/25/2013 DONE
DetailsTim Frost
Application received  3/21/2013 DONE
Application submitted via PDS Online on Mar 21 2013 2:12PM