Permit Information
Permit NumberFIR13-00141
StatusFinaled
Name SENTRY SECURITY SYSTEMS
Site Address 2879 S FRY ST
Project NameBoise Rigging
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to replace the existing fire alarm system due to instability of an old system. This permit scope of work includes sprinkler system monitoring, elevator recall and shunt trip functions, smoke and heat detectors for recall/shunt trip functions, a smoke detector above the FACP, a pull station, and a remote annunciator panel. There is no associated building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Case Summary  1/30/2014 DONE
INSP-Final Inspection5/3/20135/6/20135/6/2013APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection4/28/20134/29/20134/29/2013PFAIL
DetailsTroy Cobbley
The hvac unit in the second floor sewing room failed to shutdown when the duct smoke detector was activated. The flow switch alarms do not latch as required and the outside electric alarm bell did not function. Per Robert the 5 year elevator inspection is going to require the fire mans hat to function correctly. He would like to waite until this elevator work is complete prior to testing/finaling this permit.
Plan resubmittals received  4/16/2013  
Recieved 2 copies of "AS BUILTS" of sheets FA00, FA2.0, FA2.1
INSP-Final Inspection4/11/20134/11/20134/11/2013PFAIL
DetailsTroy Cobbley
Items tested include the phone lines, sprinkler tamper switches and elevator recall. Items needed to be approved through plan review is that the firemans hat can flash when a lobby smoke detector is activated (per code it is not allowed). Also when the wharehouse smoke detector is activated the doors open to the retail side not recall to the second floor. The duct detectors do shut down the hvac units but per Robert are wired wrong. He is going to correct this item and retest. There is one additional tamper switch not shown on the plans and the possiblility of deleting a module at the elevator. These changes will need to be shown on as-builts. I notified the building owner that the annual inspections of the sprinkler systems was overdue. He made a phone call to get the work scheduled.
Telephone call  4/5/2013 DONE
DetailsChristina Prado
called Robert to advise permit is ready and gave fees due
Permit Ready to Issue  4/5/2013 DONE
DetailsChristina Prado
Inspection Record Card- Fire4/5/2013 4/5/2013 DONE
DetailsChristina Prado
Issue and Print Permit  4/5/2013 DONE
DetailsBarbara Stitt
Miscellaneous action  4/4/2013 DONE
I recieved an email from Mary Froemke letting me know that the B occupant load on the 2nd floor was 88.
1st review completed  4/4/2013 PASS
Alarm Plan Check4/4/2013 4/4/2013 PASS
DetailsStephanie L. Cobbley
Plans approved with review comments.
PLANS TAKEN FRONT DESK ALARM  4/4/2013 DONE
Approve plans taken to permit technician for processing.
Plan assigned to (Stephanie)3/26/2013 4/4/2013 DONE
DetailsStephanie L. Cobbley
Miscellaneous action  4/2/2013 DONE
Sent an email to Mary Froemke requesting the occupant load (was not provided on permit application). I explained in the email that this is a replacement system, therefore the fire alarm system requirements must be evaluated based on current code. There are no records in our data base, however Ada County Land Records indicates this is a two-story business/warehouse (one tenant) that has 38,400 sqft per floor. Depending on how the occupant load was determined, if there is more than 100 occupant load for the 'B' portion of the building on the 2nd floor, a full manual fire alarm system will be required in this building. As it is, only sprinkler monitoring with elevator recall and HVAC monitoring has been submitted. I will need to wait to complete the review until after an accurate occupant load (specifically for the group B portion) has been provided.
Application received  3/26/2013