Permit Information
Permit NumberFIR13-00143
StatusFinaled
Name TRI STATE ELECTRIC
Site Address 1001 E PARKCENTER BLVD
Project NameWarehouse – Formerly Kmart
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to replace an existing panel that is failing. This permit scope of work includes sprinkler monitoring (three risers), a smoke detector above the FACP, and a pull station. No HVAC was shown. If duct detectors are required for HVAC shutdown/monitoring, a plan modification will be required. There is no associated building permit.
NOTE: This building is unoccupied and is therefore being treated as a sprinkler monitored building. Once the building is occupied, it will need to be re-evaluated for manual system requirements.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Case Summary  1/30/2014 DONE
INSP-Final Inspection4/30/20135/1/20135/1/2013APASS
DetailsForrest France
Noted correction items finished. Fire alarm permit finaled.
INSP-Final Inspection4/25/20134/26/20134/26/2013APART
DetailsForrest France
Wall post indicator valves must report as a supervisory condition. Remainder of fire alarm work passed inspection.
Miscellaneous action  4/18/2013 DONE
The applicant sent an email requesting to defer the annunciator requirement until the building is occupied by a tenant. I let him know that if you can see the fire alarm panel from the main entrance/front entry of the building, then we can defer the annunciator requirement in this case.
INSP-Final Inspection4/5/20134/10/20134/10/2013AFAIL
DetailsForrest France
Provide remote annunciator per review notes item #1, PIV is not electronically supervised, provide lock and label at the panel breaker. Per contractor, offsite monitoring could not be verified.
Telephone call  4/5/2013 DONE
DetailsChristina Prado
Called Rob to advise permit is ready and gave fees due
Permit Ready to Issue  4/5/2013 DONE
DetailsChristina Prado
Inspection Record Card- Fire4/5/2013 4/5/2013 DONE
DetailsChristina Prado
Issue and Print Permit  4/5/2013 DONE
Plan assigned to (Stephanie)3/28/2013 4/4/2013 DONE
DetailsStephanie L. Cobbley
1st review completed  4/4/2013 PASS
Alarm Plan Check4/4/2013 4/4/2013 PASS
DetailsStephanie L. Cobbley
Plans approved with redlines and review comments
PLANS TAKEN FRONT DESK ALARM  4/4/2013 DONE
Approved plans taken to the permit technician for processing.
Application received  3/28/2013 DONE
DetailsBarbara Stitt