Miscellaneous action | | | 9/25/2013 | | DONE |
|
|
|
Scanned application and product submittal into Tidemark and Onbase
|
INSP-Final Inspection | 4/15/2013 | 4/16/2013 | 4/17/2013 | A | PASS |
Forrest France
|
|
|
Correction items verified, re-inspection items passed. Fire alarm permit finaled.
|
INSP-Alarm Testing | 4/10/2013 | 4/12/2013 | 4/12/2013 | A | PART |
Forrest France
|
|
|
Completed fire alarm testing of the new panel and associated devices. Program issues resloved while on site, offsite monitoring verified and data entry adjusted. Final pending replacement of a non-functional SD at the panel, provide raceway for exposed wire to panel, label batteries. SCADA does not initiate a supervisory condition.
|
Inspection Record Card- Fire | 4/10/2013 | | 4/10/2013 | | DONE |
Tisha Gallop
|
|
|
|
Permit Ready to Issue | | | 4/10/2013 | | DONE |
Tisha Gallop
|
|
|
|
Telephone call | | | 4/10/2013 | | DONE |
Tisha Gallop
|
|
|
called Wayne and left vm permit is ready, fee and need to verify correct address for Benchmark Elec.
|
Issue and Print Permit | | | 4/10/2013 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 4/3/2013 | | 4/9/2013 | | DONE |
Stephanie L. Cobbley
|
|
|
|
1st review completed | | | 4/9/2013 | | PASS |
|
|
|
|
Alarm Plan Check | 4/9/2013 | | 4/9/2013 | | PASS |
Stephanie L. Cobbley
|
|
|
Plans approved with redlines and review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 4/9/2013 | | DONE |
|
|
|
Approved plans taken to permit technician for processing.
|
Application received | | | 4/2/2013 | | DONE |
|
|
|
Application submitted via PDS Online on Apr 2 2013 2:59PM
|