Permit Information
Permit NumberFIR13-00162
StatusFinaled
Name DOHERTY ELECTRIC
Site Address 200 W FRONT ST
Project NameAda County Courthouse Appeals
Customer Number 
ePlanReviewNo
Description
This quick permit is to provide a horn/strobe in a new open office/waiting area on the 1st floor due to a tenant improvement. Approval is subject to field measurement of the EOL voltage drop. The voltage drop calculations are based on a 10% drop, therefore the minimum acceptable voltage is 21.6V with the AC power off. Any measurement below this voltage will be considered insufficient to run the NACs at the end of useful battery life of 20.4V (per UL 864, Standard for Control Units for Fire Signaling Systems). See NFPA 72 2010 Handbook 18.3.2.3 for further assistance with calculations. The installing contractor shall have available at final inspection a voltage meter and measure end of line voltages; witnessed by the field inspector. There are no written review comments. Associated building permit: BLD13-00222.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  9/25/2013 DONE
Scanned application into Tidemark and Onbase
INSP-Final Inspection4/12/20134/15/20134/15/2013APASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection4/12/20134/15/20134/15/2013PPASS
DetailsTroy Cobbley
Permit finaled
Permit Ready to Issue  4/12/2013  
Inspection Record Card- Fire4/12/2013 4/12/2013 DONE
DetailsDarla L Downs
Telephone call  4/12/2013  
4-12-13 called Mike -Doherty Electric permit ready and fee given ///dld
Issue and Print Permit  4/12/2013 DONE
Plan assigned to (Stephanie)4/8/2013 4/11/2013 DONE
DetailsStephanie L. Cobbley
Plan resubmittals received  4/11/2013 DONE
Miscellaneous action  4/11/2013 DONE
Received scaled drawing/revised with dimension lines shown and a statement that there are notification devices in existing areas that provide additional coverage.
Alarm Plan Check4/11/2013 4/11/2013 PASS
DetailsStephanie L. Cobbley
Quick permit resubmittal approved - no written review comments
PLANS TAKEN FRONT DESK ALARM  4/11/2013 DONE
Approved plans taken to permit technician for processing.
1st review completed  4/9/2013 FAIL
Alarm Plan Check4/9/2013 4/9/2013 FAIL
DetailsStephanie L. Cobbley
Quick permit plans denied - no written review comments. The floorplans were not to scale, therefore notification coverage could not be verified. The building permit provided is for the 1st floor, however this quick permit scope of work is on the 2nd floor - clarification needed. More information is needed in the project description (i.e. why is the notification being added - was a wall moved, did a room type change, no room names are shown). Resubmit with checklist items complete (i.e. north arrow, scaled bar graph, plans to 1/8"=1'-0", indicate half-walls, show existing covereage in areas open to the new coverage area).
Miscellaneous action  4/9/2013 DONE
Applicant emailed with detailed information as to why the plans have been denied. No written review comments (quick permit)
Application received  4/8/2013