Case Summary | | | 1/29/2014 | | |
|
|
|
|
INSP-Final Inspection | 10/9/2013 | 10/10/2013 | 10/10/2013 | A | PASS |
Forrest France
|
|
|
Fire alarm permit finaled.
|
INSP-Alarm Testing | 10/9/2013 | 10/9/2013 | 10/9/2013 | P | PASS |
Forrest France
|
|
|
Completed remainder of alarm testing at the gatehouse including previous corrections and adjustment items. Override switch at the panel MP has been removed.
|
INSP-Alarm Testing | 10/8/2013 | 10/8/2013 | 10/9/2013 | P | FAIL |
Forrest France
|
|
|
Correction items incomplete at the time of requested inspection.
|
INSP-Alarm Testing | 10/8/2013 | 10/8/2013 | 10/8/2013 | A | PART |
Forrest France
|
|
|
|
INSP-Final Inspection | 10/1/2013 | 10/4/2013 | 10/4/2013 | P | PART |
Forrest France
|
|
|
Completed fire alarm testing for buildings 5,6,7, 12 and 14. Reinspection for ADA room 1013, room number changes, and programing at buildings 5-7 also completed.
|
INSP-Final Inspection | 9/30/2013 | 10/1/2013 | 10/1/2013 | A | PART |
Forrest France
|
|
|
Completed fire alarm testing for buildings 8, 9, 10, and 11. Also finished reinspection for previous correction items at building 4. Correction and adjustment items noted today include; non-functional visual notification at ADA unit 1013, plans show incorrect room numbers for FACP units in buildings 6 and 9, MP stations for panel at buildings 5,6, and 7 did not activate horn strobes.
|
INSP-Alarm Testing | 9/30/2013 | 9/30/2013 | 9/30/2013 | P | NR |
Forrest France
|
|
|
Pending noted corrections at building #4
|
INSP-Final Inspection | 9/27/2013 | 9/27/2013 | 9/27/2013 | P | FAIL |
Troy Cobbley
|
|
|
Todays inspection was for Building #4. See the city approved plans for corrections required.
|
INSP-Alarm Testing | 9/26/2013 | 9/26/2013 | 9/26/2013 | P | PART |
Forrest France
|
|
|
Fire alarm testing completed for buildings 1,2 and 3.
|
INSP-Final Inspection | 9/24/2013 | 9/25/2013 | 9/26/2013 | P | FAIL |
Forrest France
|
|
|
Gatehouse system inspection items inlcude; provde H/S at the workshop, SD at the 1st floor office needs relocated away from the HVAC diffuser, change descriptor at the 2nd floor SD storage room, alarm verification feature appears to be enabled for system smokes, panel map needs to include initiating device locations per review note #26, provide knox box per review comment #27, need FD approval for the toggle switch at the main panel MP. HD not tested at this time. Notification appliances and manual pull stations tested okay.
|
CHANGE STATUS TO (ISS) | | | 9/24/2013 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 9/23/2013 | | DONE |
Christina Prado
|
|
|
|
Inspection Record Card- Fire | 9/23/2013 | | 9/23/2013 | | DONE |
Christina Prado
|
|
|
|
Telephone call | | | 9/23/2013 | | DONE |
Christina Prado
|
|
|
Called Taylor Bros to advise permit is ready for pick and gave fees due
|
Plan assigned to (Lee) | 9/18/2013 | | 9/20/2013 | | DONE |
Lee G Meredith
|
|
|
|
Alarm Plan Check | 9/20/2013 | | 9/20/2013 | | FAIL |
Lee G Meredith
|
|
|
Plan mod review failed. Original requirements not met.
|
Miscellaneous action | | | 9/20/2013 | | DONE |
Lee G Meredith
|
|
|
Emailed applicant plan mod review comments.
|
Telephone call | | | 9/20/2013 | | DONE |
|
|
|
called Taylor Bros to advise plans have been denied and resubs are needed
|
Meeting | | | 9/20/2013 | | DONE |
Lee G Meredith
|
|
|
Michael from Taylor Brothers came by to pick up. failed plan mod submittal. We reviewed the plans originally marked up and approved by Stephanie Cobbley. He noted a few variances. 1) Forrest was on site to answer field questions. During that visit, Michael indicated that Forrest allowed the annunciaor to be eliminated due to the fie alarm panel actually being in the near proximity of the entry. 2) a wall at the top of the stairs of the Gate House looked like it was blocking visual notification. Michael indicated that the wall is half height and does not block. 3) a small room behind the dryers looked like it would need visual notification. Michael indicated that it is not a common or public access area since it is onluy used to access that back side of the dryers for service and maintenance work. All 3 items are to be field verified. Plan mod is being reviewed again after this discussion.
|
Alarm Plan Check | 9/20/2013 | | 9/20/2013 | | PASS |
Lee G Meredith
|
|
|
Plan mod approved as noted.
|
PLANS TAKEN FRONT DESK ALARM | | | 9/20/2013 | | DONE |
Lee G Meredith
|
|
|
|
Plan resubmittals received | | | 9/18/2013 | | DONE |
Christina Prado
|
|
|
**PLAN MOD** Received two sets of revised apps, checklist, calcs, docs and related submittal docs: Taken to Lee for review
|
Miscellaneous action | | | 8/23/2013 | | DONE |
Lee G Meredith
|
|
|
Received an email from Mary Castle of Taylor Brothers indicating the owner would like to increase the number of accessible rooms from 5 to 12, which would meet current code requirements. She wanted to know if we wanted to do a plan mod or new permit. Also, she wanted to know if we wanted to do inspections at the same time or delay and provide inspections seperately. I told her that it may be more convenient to have all inspections at the same time but to proceed which ever way was more convenient to Taylor brothers and the owner. She will inform PDS which way they will proceed prior to beginning.
|
INSP-Conference | 5/15/2013 | 5/16/2013 | 5/16/2013 | P | DONE |
Forrest France
|
|
|
On site conference with contractor regarding fire alarm permit work, NFPA 72 requirements, plan review comments, field conditions, project schedule, etc.
|
Issue and Print Permit | | | 4/26/2013 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 4/24/2013 | | |
|
|
|
|
Inspection Record Card- Fire | 4/24/2013 | | 4/24/2013 | | DONE |
Darla L Downs
|
|
|
|
Telephone call | | | 4/24/2013 | | |
|
|
|
4-24-13 called left message for Taylor Brothers permit ready and fee given ///dld
|
Plan assigned to (Stephanie) | 4/10/2013 | | 4/23/2013 | | DONE |
Stephanie L. Cobbley
|
|
|
|
1st review completed | | | 4/23/2013 | | PASS |
|
|
|
|
Alarm Plan Check | 4/23/2013 | | 4/23/2013 | | PASS |
Stephanie L. Cobbley
|
|
|
Plans approved with redlines and review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 4/23/2013 | | DONE |
|
|
|
Approved redlined plans taken to permit technician for processing.
|
Application received | | | 4/10/2013 | | |
|
|
|
|