INSP-Final Inspection | 12/7/2017 | 12/7/2017 | 12/7/2017 | A | PASS |
Jim Page
|
|
|
Final fire alarm inspection for scope of work passed/complete.
|
Miscellaneous action | | | 11/29/2017 | | DONE |
|
|
|
Shane emailed a copy of the state elevator inspector's approval report and asked if this was adequate or if a Boise City inspection is still required.
|
Miscellaneous action | | | 11/27/2017 | | DONE |
Scott Arellano
|
|
|
Instructed staff to contact Fire Alarm permit applicants to call for final inspection.
|
Miscellaneous action | | | 11/27/2017 | | DONE |
|
|
|
I eamiled Dante asking him to corrdinate the outstanding east elevator recall and shunt final acceptance tests.
|
Miscellaneous action | | | 11/27/2017 | | DONE |
|
|
|
Shane Lesteberg of the local Simplex office replied to say he is working on this with Lea Electric. Indicated that the State Elevator Inspector had signed it off.
|
INSP-Final Inspection | 1/23/2017 | 1/23/2017 | 1/23/2017 | A | PART |
Jim Page
|
|
|
Partial final inspection for fire alarm system complete, permit can be finaled after inspection of east elevator recall/shunt is complete
|
INSP-Alarm Testing | 10/19/2015 | 10/19/2015 | 10/19/2015 | A | PART |
Thomas Walsh
|
|
|
Fire alarm interface with heat tracing panels that monitor heat trace of fire sprinkler piping exposed to cold temps. See FIR 13-00461 for details of heat trace inspection.
|
INSP-Alarm Testing | 7/12/2015 | 7/12/2015 | 7/12/2015 | P | PART |
Thomas Walsh
|
|
|
test of fire sprinkler system for U/G parl'king garage, including four (4) dry pipe valves protecting the under ground parking garage and two (2) dry system suppling standpipes above the parking garage, including trip tests of the DP valves, low-air alarms, tampers and waterflows. All systems tested satisfactorily. Tom Walsh and Jim Page present for this inspection.
|
FIR-Aging Inspection | 6/30/2015 | 6/30/2015 | 6/30/2015 | | CANC |
Thomas Walsh
|
|
|
Wrong permit called in for this inspection. See FIR 13-00167 for hydrotest of U/G supply line (11th street connection).
|
INSP-Conference | 8/29/2014 | 8/29/2014 | 8/29/2014 | P | CANC |
Forrest France
|
|
|
Call for access Phone #: 2089411846 >> Inspection requested via mobile web by Brian Anderson Inspection cancelled via mobile web on Friday, August 29, 2014.
|
Miscellaneous action | | | 6/13/2013 | | DONE |
Lee G Meredith
|
|
|
Confirmed to Charlie that the garage and 5th floor would require voice evac and strobes throughout due to the mixed occupancy of parking, museum and amusement park.
|
Permit Ready to Issue | | | 5/10/2013 | | DONE |
|
|
|
|
Issue and Print Permit | | | 5/10/2013 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 5/10/2013 | | 5/10/2013 | | DONE |
Christina Prado
|
|
|
|
1st review completed | | | 5/9/2013 | | PASS |
|
|
|
|
Alarm Plan Check | 5/9/2013 | | 5/9/2013 | | PASS |
Stephanie L. Cobbley
|
|
|
plans approved with redlines and review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 5/9/2013 | | DONE |
|
|
|
updated in project dox
|
Plan assigned to (Stephanie) | 4/25/2013 | | 4/25/2013 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Application received | | | 4/22/2013 | | DONE |
|
|
|
Application submitted via PDS Online on Apr 22 2013 1:18PM
|