INSP-Final Inspection | 1/15/2014 | 1/16/2014 | 1/16/2014 | A | PASS |
Forrest France
|
|
|
Correction items completed. Fire alarm permit approved for final status.
|
INSP-Final Inspection | 1/14/2014 | 1/15/2014 | 1/15/2014 | A | CANC |
Forrest France
|
|
|
As early as possible Phone #: 2089411846 >> Inspection requested via mobile web by Brian Aa Inspection cancelled via mobile web on Wednesday, January 15, 2014.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/26/2013 | | |
Lee G Meredith
|
|
|
|
CHANGE STATUS TO (ISS) | | | 11/26/2013 | | DONE |
|
|
|
|
INSP-Final Inspection | 11/22/2013 | 11/25/2013 | 11/25/2013 | A | PART |
Forrest France
|
|
|
Final pending plan modification approvals and inspection for relays to existing fire smoke dampers to remain functional at the east garage.
|
INSP-Final Inspection | 11/20/2013 | 11/21/2013 | 11/25/2013 | A | FAIL |
Forrest France
|
|
|
Inspection completed 11/21. SD at the elevator lobbies in the new parking garage will not meet listing due to missing HVAC. Provide verification existing fire/smoke dampers are not required or interface with panel per plan. Provide a plan modification due to necessary changes.
|
Plan resubmittals received | | | 11/25/2013 | | DONE |
Lee G Meredith
|
|
|
Resubmittal received. electronic smoke detectors in unheated elevator lobbies changed to non electronic heat detectors.
|
Alarm Plan Check | 11/25/2013 | | 11/25/2013 | | PASS |
Lee G Meredith
|
|
|
|
Meeting | | | 11/22/2013 | | DONE |
|
|
|
On site with Scott Arellano and Jim Storey to review existing fire dampers in existing garage that are not functional. Scott will discuss whether to have the dampers repaired or removed with Jason Blais and John Menard.
|
Telephone call | | | 11/20/2013 | | DONE |
|
|
|
Received a phone call from Forest regarding the use of electronic smoke detectors in un-heated elevator lobbies. I informed him that it would not be acceptable since the detectors would be outside of the temperature range of their UL listing. An acceptable design would be to use non electronic heat detectors monitored by a module that was located inside of a heated area.
|
Permit Ready to Issue | | | 5/1/2013 | | |
|
|
|
|
Inspection Record Card- Fire | 5/1/2013 | | 5/1/2013 | | DONE |
Darla L Downs
|
|
|
|
Issue and Print Permit | | | 5/1/2013 | | DONE |
|
|
|
|
1st review completed | | | 4/30/2013 | | PASS |
|
|
|
|
Alarm Plan Check | 4/30/2013 | | 4/30/2013 | | PASS |
Stephanie L. Cobbley
|
|
|
approved with mark-ups and review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 4/30/2013 | | DONE |
|
|
|
updated in project dox
|
Plan assigned to (Stephanie) | 4/23/2013 | | 4/23/2013 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Application received | | | 4/22/2013 | | DONE |
|
|
|
Application submitted via PDS Online on Apr 22 2013 3:11PM
|