Permit NumberFIR13-00180
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 3201 W AIRPORT WAY
Project NameBOI Parking Garage
Customer Number 
ePlanReviewYes
Description
BOI Parking Garage job is to add a new FACP panel and provide elevator control interface. Design made by CH2Mhill.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/15/20141/16/20141/16/2014APASS
DetailsForrest France
Correction items completed. Fire alarm permit approved for final status.
INSP-Final Inspection1/14/20141/15/20141/15/2014ACANC
DetailsForrest France
As early as possible Phone #: 2089411846 >> Inspection requested via mobile web by Brian Aa Inspection cancelled via mobile web on Wednesday, January 15, 2014.
PLANS/APPL TAKEN TO FRONT DESK  11/26/2013  
DetailsLee G Meredith
CHANGE STATUS TO (ISS)  11/26/2013 DONE
INSP-Final Inspection11/22/201311/25/201311/25/2013APART
DetailsForrest France
Final pending plan modification approvals and inspection for relays to existing fire smoke dampers to remain functional at the east garage.
INSP-Final Inspection11/20/201311/21/201311/25/2013AFAIL
DetailsForrest France
Inspection completed 11/21. SD at the elevator lobbies in the new parking garage will not meet listing due to missing HVAC. Provide verification existing fire/smoke dampers are not required or interface with panel per plan. Provide a plan modification due to necessary changes.
Plan resubmittals received  11/25/2013 DONE
DetailsLee G Meredith
Resubmittal received. electronic smoke detectors in unheated elevator lobbies changed to non electronic heat detectors.
Alarm Plan Check11/25/2013 11/25/2013 PASS
DetailsLee G Meredith
Meeting  11/22/2013 DONE
On site with Scott Arellano and Jim Storey to review existing fire dampers in existing garage that are not functional. Scott will discuss whether to have the dampers repaired or removed with Jason Blais and John Menard.
Telephone call  11/20/2013 DONE
Received a phone call from Forest regarding the use of electronic smoke detectors in un-heated elevator lobbies. I informed him that it would not be acceptable since the detectors would be outside of the temperature range of their UL listing. An acceptable design would be to use non electronic heat detectors monitored by a module that was located inside of a heated area.
Permit Ready to Issue  5/1/2013  
Inspection Record Card- Fire5/1/2013 5/1/2013 DONE
DetailsDarla L Downs
Issue and Print Permit  5/1/2013 DONE
1st review completed  4/30/2013 PASS
Alarm Plan Check4/30/2013 4/30/2013 PASS
DetailsStephanie L. Cobbley
approved with mark-ups and review comments
PLANS TAKEN FRONT DESK ALARM  4/30/2013 DONE
updated in project dox
Plan assigned to (Stephanie)4/23/2013 4/23/2013 DONE
DetailsStephanie L. Cobbley
Application received  4/22/2013 DONE
Application submitted via PDS Online on Apr 22 2013 3:11PM